Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the remarkable ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker, a paramount innovation for modern outdoor distribution networks. Affectionately dubbed the 'circuit breaker,' this advanced piece of switchgear is meticulously designed for a 12kV rated voltage, complementing a robust three-phase AC at 50Hz. This dynamic powerhouse excels at skillfully handling the interruption and reconnection of load currents, overload currents, and short circuit currents within power grids. Equipped with state-of-the-art overload and short circuit protective capabilities, it effortlessly fulfills control and measurement demands while offering sophisticated remote control and monitoring functions. Its expansive application scope includes substations, industrial sectors, and mining enterprise distribution systems, making it the superior choice for environments necessitating frequent operations. This ensures unrivaled control, efficiency, and reliability.
Structural Features:
Meticulously crafted, the circuit breaker showcases an elegantly refined three-phase pillar dry design;
Expertly engineered with a fully enclosed structure, it provides outstanding sealing, exemplary moisture resistance, and impressive anti-condensation properties, making it perfect for high-temperature and humid environments;
Utilizes state-of-the-art vacuum arc extinguishing technology, offering unparalleled insulation reliability;
Ensures impeccable opening and closing performance, guaranteeing safety with no risk of combustion or explosion;
Designed to be compact and lightweight, requiring no maintenance while boasting an impressive lifespan;
Features versatile operation with manual, electric, or remote control options at your disposal;
The operating mechanism is meticulously sealed at the switch box's base, providing robust protection against outdoor environmental corrosion;
Showcases an innovative and simplified design featuring a restless mechanism, ensuring reliable dynamic performance, a compact structure, and an astonishing service life that reaches up to an incredible 10,000 cycles.
Main Technical Parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |