Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker, prized among distribution switchgear enthusiasts for its unmatched capabilities and affectionately dubbed the 'circuit breaker.' With its impressive operational standard at a rated voltage of 12kV and a formidable three-phase AC frequency of 50Hz, this breaker stands unparalleled. It expertly orchestrates the interruption and reconnection of load currents, overload currents, and short circuit currents within power grids. Equipped with cutting-edge overload and short circuit protection, it meets stringent control and measurement criteria. Its advanced design allows seamless remote control and monitoring, making it indispensable for diverse settings including substations, industrial areas, and mining enterprise distribution systems. Its durability and reliability make it the ideal choice for environments where operations are frequent and paramount.
Structural features:
Crafted with unparalleled precision, this circuit breaker stands out with its sophisticated three-phase pillar dry design.
Meticulously engineered with a fully enclosed structure, it ensures superior sealing, boasting exceptional moisture resistance and anti-condensation features, rendering it an optimal choice for high-temperature and humid regions.
Employs cutting-edge vacuum arc extinguishing technology, offering unrivaled insulation reliability and operational security.
Guarantees impeccable opening and closing performance, prioritizing safety with zero risk of combustion or explosion.
Boasts a compact, lightweight design that is maintenance-free, promising an impressive service life that exceeds expectations.
Showcases operational versatility with manual, electric, or remote control options, adapting seamlessly to user preferences.
The operating mechanism is meticulously encased at the base of the switch box, providing robust protection against the elements, preventing environmental corrosion.
Features a novel, simplistic design with a revolutionary restless mechanism, ensuring reliable dynamic performance, compactness, and an astounding service life reaching up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |