Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 outdoor high voltage vacuum circuit breaker, fondly referred to as the 'circuit breaker.' This remarkable outdoor distribution switchgear is engineered to operate seamlessly at a rated voltage of 12kV, powered by a formidable three-phase AC of 50Hz. This adaptable circuit breaker excels in managing the interruption and connection of load current, overload current, and short circuit current within the power grid. It is designed with exceptional advanced overload and short circuit protective capabilities, effortlessly meeting control and measurement criteria while offering sophisticated remote control and monitoring features. Widely utilized in substations, industrial arenas, and mining enterprise distribution systems, this circuit breaker provides unmatched control and operation—perfectly suited for environments demanding frequent operations.
Structural features:
Meticulously crafted with precision, the circuit breaker boasts a sophisticated three-phase pillar dry design;
Ingeniously engineered with a fully enclosed structure, it guarantees superior sealing, outstanding moisture resistance, and remarkable anti-condensation properties, making it the ideal choice for high-temperature and humid regions;
Incorporates cutting-edge vacuum arc extinguishing technology, ensuring unparalleled insulation reliability;
Provides flawless opening and closing performance, ensuring safety with zero risk of combustion or explosion;
Boasting a compact and lightweight build, it requires no maintenance and promises an extraordinary lifespan;
Offers versatility in operation with options for manual, electric, or remote control;
The operating mechanism is painstakingly sealed at the base of the switch box, effectively protecting against outdoor environmental corrosion;
Presents a novel and simple design infused with a restless mechanism, ensuring reliable dynamic performance, a compact form, and an incredible service life of up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |