Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker, fondly referred to as the 'circuit breaker.' This exceptional piece of outdoor distribution switchgear is masterfully engineered to operate at a rated voltage of 12kV with a formidable three-phase AC of 50Hz. It is a versatile powerhouse, proficiently managing the interruption and connection of load current, overload current, and short circuit current within the electrical grid. With its cutting-edge features, it offers advanced overload and short circuit protection, adeptly meeting control and measurement requirements while providing sophisticated remote control and monitoring capabilities. Its extensive application spans substations, industrial arenas, and mining enterprise distribution systems, offering unmatched control and operation, making it ideal for settings demanding frequent operations.
Structural features:
Crafted with precision, this circuit breaker reveals a robust three-phase pillar dry design;
Expertly engineered with a fully enclosed structure, it ensures superior sealing, remarkable moisture resistance, and anti-condensation properties, making it the ultimate selection for high-temperature and humid areas;
Employing cutting-edge vacuum arc extinguishing technology, it guarantees extraordinary insulation reliability;
This breaker promises impeccable opening and closing operation, ensuring safety with no risk of combustion or explosion;
Compact and lightweight, it requires no maintenance and guarantees an impressive operational lifespan;
Outstanding versatility in operation—offering manual, electric, or remote control options;
The operating mechanism is meticulously sealed at the base of the switch box, providing effective protection against outdoor environmental corrosion;
Featuring a novel and simplistic design, its dynamic restless mechanism assures reliable performance, a compact form, and an extraordinary service life of up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |