Customization: | Available |
---|---|
Breaking Capacity: | 12kv/24kv/40.5kv |
Type: | Current Fuse |
Still deciding? Get samples of US$ 30/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
(H) RW(F) series outdoor high voltage AC drop fuse (referred to as "fuse") is perfectly engineered for outdoor overhead distribution systems with a rated frequency of 50Hz and a rated voltage spectrum of 10kV, extending through 12/15/35/40.5. This fuse acts as an essential guardian for circuits and electrical equipment, protecting them from overloads or short circuit faults within any power system. In standard operation, the fuse is flawlessly integrated in series within the power line, ensuring it remains in a taut, tensioned state with securely locked movable joints. Upon detecting a line fault, the fault current triggers the fuse to blow, releasing the movable joint, swiftly ejecting the fuse tube, thereby disconnecting the circuit to ensure unparalleled safety for line and equipment maintenance. Enhanced with elastic contacts and arc extinguishing covers, the load type fuse elevates functionality, adeptly handling the opening and closing of load current within the power system.
The fuse meets the highest technical standards including GB / T 15166.3 - 2008 for high voltage AC fuses - Part 3: injection fuses, alongside DL / T 640 - 1997 standards for outdoor AC high voltage drop-tested fuses and their ordering technical conditions.
Working Environment:
Ambient temperature: Range from a chilly -40°C to a warm +40°C.
Relative humidity: Daily averages do not exceed 95%, while monthly averages are capped at 90%.
Altitude: Installation heights should not surpass 3000m.
Outdoor wind speed: Should not exceed a brisk 34 meters/second.
Installation site: Must be free of fire, explosion hazards, and chemical corrosive gases, ensuring a well-ventilated environment.
Note: Should your operational conditions surpass the parameters listed above, we invite you to engage with us for a tailored solution.
Technical parameters
Note: We proudly offer customization capabilities to align our products with your specific requirements.
Model |
Voltage |
Current |
Rated maximum
breaking current |
1min power frequency dry withstand
voltage |
1min power frequency wet withstand
voltage |
Rated lightning impulse withstand
voltage |
Opening and closing
load current |
XS-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
XS-15/100(200) |
15 |
||||||
PD-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
PD-15/100(200) |
15 |
||||||
(H)RW3-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW3-12/100(200) |
12 |
||||||
(H)RW4-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW4-12/100(200) |
12 |
||||||
(H)RW7-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW7-12/100(200) |
12 |
||||||
(H)RW10-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW10-12/100(200) |
12 |
||||||
(H)RW10-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW10-12F/100(200) |
12 |
||||||
(H)RW11-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
! |
(H)RW11-12/100(200) |
12 |
||||||
(H)RW11-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW11-12F/100(200) |
12 |
||||||
(H)RW12-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
45 |
30 |
105 |
/ |
(H)RW12-12/100(200) |
12 |
||||||
(H)RW12-15/100(200) |
15 |
||||||
(H)PRWG1-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)PRWG1-12F/100(200) |
12 |
||||||
(H)RW33-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW33-15/100(200) |
15 |
||||||
(H)RW5-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)RW10-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)PRWG2-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |