Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 outdoor high voltage vacuum circuit breaker, endearingly referred to as the 'circuit breaker,' a paragon of outdoor distribution switchgear engineered for a rated voltage of 12kV with a formidable three-phase AC at 50Hz. This adaptable circuit breaker excels in interrupting and connecting load current, managing overload and short circuit currents within the power grid. It features groundbreaking overload and short circuit protection, impeccably meeting control and measurement demands while offering cutting-edge remote control and monitoring capabilities. Its expansive application spans substations, industrial arenas, and mining enterprise distribution systems, delivering unrivaled control and operation—ideal for scenarios demanding frequent operations.
Structural features:
Meticulously crafted, the circuit breaker displays an innovative three-phase pillar dry design;
Engineered with a comprehensively enclosed structure, it provides exceptional sealing, superior moisture resistance, and anti-condensation properties, making it an optimal selection for high-temperature and humid locales;
Utilizes cutting-edge vacuum arc extinguishing technology, ensuring remarkable insulation reliability;
Provides impeccable opening and closing performance, guaranteeing safety with no risk of combustion or explosion;
Compact and lightweight, requiring zero maintenance, and promises an extraordinary lifespan;
Offers operational versatility with manual, electric, or remote control options available;
The operating mechanism is expertly sealed at the switch box base, effectively shielding against outdoor environmental corrosion;
Boasts a novel, simplistic design featuring a restless mechanism that ensures reliable dynamic performance, a compact form, and an astonishing service life of up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |