Customization: | Available |
---|---|
Breaking Capacity: | 12kv/24kv/40.5kv |
Type: | Current Fuse |
Still deciding? Get samples of US$ 30/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Discover the exceptional (H) RW(F) series outdoor high voltage AC drop fuse, crafted for impeccable performance in outdoor overhead distribution systems. Designed to operate at a rated frequency of 50Hz and voltage of 10kV (12/15/35/40.5), this fuse serves as the ultimate protective measure for circuits or electrical equipment experiencing overloads or short circuit faults in power systems. Seamlessly integrating into power lines in a tensioned state with a locked movable joint, the fuse is poised for action. Upon fault detection, the fault current initiates the fuse to blow, unlocking the movable joint and swiftly dropping the fuse tube to disconnect the circuit. This process ensures unparalleled safety protection, safeguarding maintenance teams and preserving line and equipment integrity. Enhanced with elastic contact and an arc extinguishing cover, the load type fuse elevates the functionality of standard designs, offering the capability to proficiently manage the power system's load current operations.
The fuse is meticulously designed to meet rigorous standards, including GB / T 15166.3 - 2008 for high voltage AC fuses - Part 3: injection fuses, and DL / T 640 - 1997 for outdoor AC high voltage drop tested fuses and fuse links ordering technical conditions. This ensures reliability, durability, and compliance with the highest technical benchmarks.
Working Environment:
Capable of withstanding a broad range of conditions, with an ambient temperature adaptability from an icy -40°C to a warm +40°C.
Relative humidity: Adapted to high humidity conditions, with a daily average not surpassing 95% and a monthly average not exceeding 90%, ensuring consistent performance.
Reliable at altitudes up to 3000 meters, maintaining optimal functionality in diverse geographical locations.
Engineered to perform in outdoor environments with wind speeds up to 34 meters per second, ensuring resilience in challenging weather.
Ideal installation sites are free from fire, explosion hazards, and chemical corrosive gases, ensuring a well-ventilated environment for optimal operation.
Note: For any conditions exceeding the above specifications, we welcome negotiations to tailor solutions that meet your specific needs.
Technical parameters
Note: We are committed to delivering customized products tailored to your precise requirements.
Model |
Voltage |
Current |
Rated maximum
breaking current |
1min power frequency dry withstand
voltage |
1min power frequency wet withstand
voltage |
Rated lightning impulse withstand
voltage |
Opening and closing
load current |
XS-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
XS-15/100(200) |
15 |
||||||
PD-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
PD-15/100(200) |
15 |
||||||
(H)RW3-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW3-12/100(200) |
12 |
||||||
(H)RW4-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW4-12/100(200) |
12 |
||||||
(H)RW7-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW7-12/100(200) |
12 |
||||||
(H)RW10-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW10-12/100(200) |
12 |
||||||
(H)RW10-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW10-12F/100(200) |
12 |
||||||
(H)RW11-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
! |
(H)RW11-12/100(200) |
12 |
||||||
(H)RW11-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW11-12F/100(200) |
12 |
||||||
(H)RW12-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
45 |
30 |
105 |
/ |
(H)RW12-12/100(200) |
12 |
||||||
(H)RW12-15/100(200) |
15 |
||||||
(H)PRWG1-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)PRWG1-12F/100(200) |
12 |
||||||
(H)RW33-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW33-15/100(200) |
15 |
||||||
(H)RW5-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)RW10-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)PRWG2-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |