Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 outdoor high voltage vacuum circuit breaker, our innovative marvel affectionately recognized as the 'circuit breaker.' This exceptional piece of engineering is a pinnacle of outdoor distribution switchgear, specifically devised to operate seamlessly at a rated voltage of 12kV while wielding a formidable three-phase AC of 50Hz. Masterfully adept, this circuit breaker excels at the interruption and reconnection of load current, overload current, and short circuit current within the power grid. It offers cutting-edge overload and short circuit protective capabilities, impeccably meeting control and measurement specifications, and is equipped with advanced remote control and monitoring features. Its extensive application range embraces substations, industrial landscapes, and mining enterprise distribution systems, delivering unmatched control and operational excellence, especially in environments characterized by frequent operational demands.
Structural features:
Meticulously crafted, the circuit breaker exhibits a sophisticated three-phase pillar dry design, ensuring optimal performance;
Designed with a fully enclosed architecture, it provides superior sealing, remarkable moisture resistance, and anti-condensation capabilities, rendering it the ideal solution for high-temperature and humid locales;
Incorporates cutting-edge vacuum arc extinguishing technology, offering exceptional insulation reliability;
Ensures impeccable opening and closing performance, prioritizing safety with zero risk of combustion or explosion;
Designed to be compact and lightweight, this circuit breaker requires no maintenance and guarantees an impressive lifespan;
Boasts remarkable operational versatility, with options for manual, electric, or remote control;
The operating mechanism is thoughtfully sealed at the switch box base, providing robust protection against environmental corrosion;
Highlights an innovative, simple design with a dynamic mechanism that ensures reliable performance, a compact structure, and an extraordinary service life reaching up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |