Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Discover the pinnacle of modern electrical engineering with the ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker. This premier solution, affectionately referred to as the 'circuit breaker,' is expertly designed for today's outdoor distribution networks. With a robust 12kV rated voltage and a resilient three-phase AC at 50Hz, this cutting-edge device is unparalleled in its ability to break and reconnect load current, overload current, and short circuit current seamlessly. It stands out with its advanced overload and short circuit protective capabilities, fully addressing control and measurement demands while integrating sophisticated remote control and monitoring functions. Its vast application spectrum extends from substations to industrial environments and mining enterprise distribution systems, making it the ideal choice for settings requiring frequent operations. This ensures unparalleled control and efficiency, rendering it an essential asset for contemporary electrical infrastructures.
Structural Features:
Exquisitely crafted with precision, the circuit breaker boasts a refined three-phase pillar dry design;
Ingeniously engineered with a completely enclosed structure, it offers exceptional sealing, unmatched moisture resistance, and anti-condensation properties, making it perfect for high-temperature and humid environments;
Employs cutting-edge vacuum arc extinguishing technology, delivering outstanding insulation reliability;
Guarantees flawless opening and closing performance, ensuring safety with zero risk of combustion or explosion;
Compact and lightweight, this sophisticated device is maintenance-free, promising an impressive lifespan;
Offers versatile operation capabilities, with manual, electric, or remote controls available for ultimate convenience;
The operating mechanism is expertly sealed at the switch box's base to effectively protect against environmental corrosion;
Presents an innovative, simplified design with a restless mechanism, ensuring reliable dynamic performance, a compact structure, and an astonishing service life reaching up to 10,000 cycles.
Main Technical Parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |