Customization: | Available |
---|---|
Breaking Capacity: | 12kv/24kv/40.5kv |
Type: | Current Fuse |
Still deciding? Get samples of US$ 30/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
(H) RW(F) series outdoor high voltage AC drop fuse, commonly referred to as the 'fuse', is meticulously engineered for outdoor overhead distribution systems. This fuse is adept at handling a rated frequency of 50Hz and a rated voltage spectrum of 10kV, extending to options like 12/15/35/40.5. It serves as an indispensable protective component for circuits or electrical equipment against power system overloads or short circuits. During normal operations, the fuse is linked in series within the power line, maintained in a taut state with a secure movable joint. Upon a system fault, the resulting surge in fault current triggers the fuse to blow, prompting the joint to disengage. The fuse tube then swiftly descends, severing the circuit and ensuring comprehensive safety protection for line and equipment maintenance. Enhanced with a load type fuse, featuring elastic contacts and an arc extinguishing cover, it adeptly manages both opening and closing of load currents within the power system.
The fuse aligns with esteemed technical standards like GB / T 15166.3 - 2008 for high voltage AC fuses - Part 3: injection fuses, and DL / T 640 - 1997 for outdoor AC high voltage drop-tested fuses, including the stringent technical conditions for fuse links ordering.
Working Environment:
Ambient temperature: Spanning from a chilling -40°C to a balmy +40°C, ensuring adaptability across diverse climates;
Relative humidity: With a daily average cap of 95% and a monthly average not surpassing 90%, guaranteeing optimal performance in humid conditions;
Altitude: The operational threshold is an elevation of up to 3000 meters, suitable for various geographical terrains;
Outdoor wind speed: Operates efficiently with wind speeds up to 34 meters per second, ensuring resilience against high winds;
Installation site: Ideal for areas devoid of fire and explosion hazards, free from chemical corrosive gases, and favorably ventilated to support longevity and safety.
Note: Should typical usage conditions exceed these limits, users are encouraged to discuss customized solutions with us to ensure optimal equipment functionality.
Technical parameters
Note: Our company is committed to tailoring products to meet specific user requirements, ensuring satisfaction and precision.
Model |
Voltage |
Current |
Rated maximum
breaking current |
1min power frequency dry withstand
voltage |
1min power frequency wet withstand
voltage |
Rated lightning impulse withstand
voltage |
Opening and closing
load current |
XS-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
XS-15/100(200) |
15 |
||||||
PD-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
PD-15/100(200) |
15 |
||||||
(H)RW3-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW3-12/100(200) |
12 |
||||||
(H)RW4-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW4-12/100(200) |
12 |
||||||
(H)RW7-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW7-12/100(200) |
12 |
||||||
(H)RW10-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW10-12/100(200) |
12 |
||||||
(H)RW10-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW10-12F/100(200) |
12 |
||||||
(H)RW11-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
! |
(H)RW11-12/100(200) |
12 |
||||||
(H)RW11-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW11-12F/100(200) |
12 |
||||||
(H)RW12-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
45 |
30 |
105 |
/ |
(H)RW12-12/100(200) |
12 |
||||||
(H)RW12-15/100(200) |
15 |
||||||
(H)PRWG1-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)PRWG1-12F/100(200) |
12 |
||||||
(H)RW33-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW33-15/100(200) |
15 |
||||||
(H)RW5-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)RW10-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)PRWG2-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |