Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The ZW32-12 outdoor high voltage vacuum circuit breaker, fondly referred to as the 'circuit breaker,' stands as a paragon of outdoor distribution switchgear. With a dynamic rated voltage of 12kV and an impressive three-phase AC of 50Hz, this circuit breaker is a masterpiece in managing the interruption and connection of load currents, handling overload currents, and adeptly managing short circuit currents within the power grid. It boasts cutting-edge overload and short circuit protective features, meeting control and measurement needs with grace, while offering sophisticated remote control and monitoring capabilities. Its widespread application extends to substations, industrial environments, and mining enterprises, offering unrivaled control and operation ideal for settings with frequent usage.
Structural features:
Meticulously crafted, the circuit breaker showcases an innovative three-phase pillar dry design, epitomizing engineering excellence;
Constructed with a fully enclosed structure, it provides exceptional sealing, moisture resistance, and anti-condensation properties, making it the optimal choice for high-temperature and humid climates;
Utilizes pioneering vacuum arc extinguishing technology, ensuring superior insulation reliability;
Offers impeccable opening and closing performance, guaranteeing safety with no risk of combustion or explosion;
Remarkably compact and lightweight, requiring zero maintenance, and promises an impressive lifespan;
Operational versatility with manual, electric, or remote control options available;
The operating mechanism is carefully sealed at the base of the switch box, providing robust protection against outdoor environmental corrosion;
Features a novel, minimalist design with a restless mechanism that assures dependable dynamic performance, compact construction, and a remarkable service life reaching up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |