Zinc oxide arrester is a new type of fully sealed and highly reliable lightning protection device for 10kV power distribution system. It is made of zinc oxide valve column, upper and lower electrodes, and silicone rubber integrally molded. It has the following characteristics:
The specially developed valve plate and reasonable core parameters are used to ensure that the core can reliably withstand arc grounding, PT resonance and various operating overvoltages, and can operate safely for a long time under line voltage, 2.5 times and 3 times power frequency overvoltage. The voltage withstand time is 1 to 3 orders of magnitude higher than international requirements.
Main Characteristics Of Jacket Materials And Product Usage Environment:
Item |
Unit |
Norm |
Shore Hardness A |
/ |
60 |
Tensile Strength |
mpa |
≥35 |
Breaking Elongation |
% |
≥250 |
Oxygen Index |
/ |
45 |
Resistivity |
Ω.m |
≥1×1013 |
Breakdown Strength |
MV/m |
≥25 |
Tracking |
kV |
4.5 |
Durability |
Not less than 20 years |
Working Environment:
Suitable for indoor and outdoor;
The altitude does not exceed 3000m;
Ambient temperature: -40C +60C;
The power supply frequency is not less than 48Hz, not more than 62Hz;
The power frequency voltage applied between the arrester terminals for a long time is not excessive
Seismic intensity not exceeding 8 degrees.
Outdoor wind speed not exceeding 35 meters/second;
Note:
When the above normal use conditions are exceeded, the user can negotiate with the company.
Main technical parameters
Model |
Nominal Voltage (rms) |
Rated Voltage Of Arrester (rms) |
Continuous Operating Voltage (rms) |
DC 1mA reference voltage |
The residual voltage under nominal discharge current |
Steep wave impact residual voltage |
2ms square wave flow capacity |
Operation Place |
YH5WS-3.8/17 |
3 |
3.8 |
2.0 |
7.5 |
17.0 |
19.6 |
100 |
Distribution Type |
YH5WS-5/15 |
3 |
5 |
4.0 |
7.5 |
15.0 |
17.3 |
150 |
|
YH5WS-7.6/30 |
6 |
7.6 |
4.0 |
15.0 |
15.0 |
34.5 |
100 |
|
YH5WS-10/30 |
6 |
10 |
8.0 |
15.0 |
30.0 |
34.6 |
150 |
|
YH5WS-12.7/50 |
10 |
12.7 |
10 |
26.0 |
50.0 |
57.5 |
100 |
|
YH5WS-16.5/50 |
10 |
16.5 |
12.7 |
26.0 |
50.0 |
57.5 |
100 |
|
YH5WS-17/50 |
10 |
17 |
13.6 |
26.0 |
50.0 |
57.5 |
150 |
|
YH5WS-17/45 |
10 |
17 |
13.6 |
25.0 |
45.0 |
/ |
250 |
|
YH10WS-17/45 |
10 |
17 |
13.6 |
25.0 |
45.0 |
/ |
400 |
|
YH5WZ-5/13.5 |
3 |
5 |
4.0 |
7.2 |
13.5 |
15.5 |
200 |
Power Station Type |
YH5WZ-7.6/27 |
6 |
7.6 |
4.0 |
14.4 |
27.0 |
31.0 |
150 |
|
YH5WZ-10/27 |
6 |
10 |
8.0 |
14.4 |
27.0 |
31.0 |
200 |
|
YH5WZ-42/134 |
35 |
42 |
23.4 |
73 |
134 |
154 |
150 |
|
YH5WZ-12.7/45 |
10 |
12.7 |
6.6 |
24.0 |
45.0 |
51.8 |
150 |
|
YH5WZ-16.5/45 |
10 |
16.5 |
13.2 |
24.0 |
45.0 |
51.8 |
150 |
|
YH5WZ-17/45 |
10 |
17 |
13.6 |
24.0 |
45.0 |
51.8 |
200 |
|
YH5WZ-51/134 |
35 |
51 |
40.8 |
73.0 |
134 |
154 |
400 |
|
YH10WZ-17/45 |
10 |
17 |
13.6 |
24.0 |
45.0 |
51.8 |
200 |
|
YH10WZ-51/134 |
35 |
51 |
40.8 |
73.0 |
134 |
154 |
400 |
|
YH5WR-5/13.5 |
3 |
5 |
4.0 |
7.2 |
13.5 |
/ |
400 |
Capacitive Type |
YH5WR-7.6/27 |
6 |
7.6 |
4.0 |
13.8 |
27.0 |
/ |
400 |
|
YH5WR-10/27 |
6 |
10 |
8.0 |
14.4 |
27.0 |
/ |
400 |
|
YH5WR-12.7/45 |
10 |
12.7 |
6.6 |
23.0 |
45.0 |
/ |
400 |
|
YH5WR 17/45 |
10 |
17 |
13.6 |
24.0 |
45.0 |
/ |
400 |
|
YH5WX-51/134 |
35 |
51 |
40.8 |
73 |
134.0 |
154 |
400 |
Line type |
YH1.5W-30/80 |
35 |
30 |
24 |
44 |
80.0 |
/ |
600 |
Neutral Type |
Note:Polymeric
Model |
Nominal Voltage (rms) |
Rated Voltage Of Arrester (rms) |
Continuous Operating Voltage (rms) |
DC 1mA Reference Voltage |
The Residual Voltage Under Nominal Discharge Current |
Steep Wave Impact Residual Voltage |
2ms Square Wave Flow Capacity |
Operation Place |
Y5WS-5/15 |
3 |
5 |
4.0 |
7.5 |
15.0 |
17.3 |
150 |
Distribution Type |
Y5WS-7.6/30 |
6 |
7.6 |
4.0 |
15.0 |
15.0 |
34.5 |
100 |
|
Y5WS-10/30 |
6 |
10 |
8.0 |
15.0 |
30.0 |
34.6 |
150 |
|
Y5WS-12.7/50 |
10 |
12.7 |
10 |
26.0 |
50.0 |
57.5 |
100 |
|
Y5WS-16.5/50 |
10 |
16.5 |
12.7 |
26.0 |
50.0 |
57.5 |
100 |
|
Y5WS-17/50 |
10 |
17 |
13.6 |
26.0 |
50.0 |
57.5 |
150 |
|
Y5WZ-5/13.5 |
3 |
5 |
4.0 |
7.2 |
13.5 |
15.5 |
200 |
Power Station Type |
Y5WZ-7.6/27 |
6 |
7.6 |
4.0 |
14.4 |
27.0 |
31.0 |
150 |
|
Y5WZ-10/27 |
6 |
10 |
8.0 |
14.4 |
27.0 |
31.0 |
200 |
|
Y5WZ-42/134 |
35 |
42 |
23.4 |
73 |
134 |
154 |
150 |
|
Y5WZ-12.7/45 |
10 |
12.7 |
6.6 |
24.0 |
45.0 |
51.8 |
150 |
|
Y5WZ-16.5/45 |
10 |
16.5 |
13.2 |
24.0 |
45.0 |
51.8 |
150 |
|
Y5WZ-17/45 |
10 |
17 |
13.6 |
24.0 |
45.0 |
51.8 |
200 |
|
Y5WZ-51/134 |
35 |
51 |
40.8 |
73.0 |
134 |
154 |
400 |
|
Y5WR-5/13.5 |
3 |
5 |
4.0 |
7.2 |
13.5 |
/ |
400 |
Capacitive Type |
Y5WR-7.6/27 |
6 |
7.6 |
4.0 |
13.8 |
27.0 |
/ |
400 |
|
Y5WR-10/27 |
6 |
10 |
8.0 |
14.4 |
27.0 |
/ |
400 |
|
Y5WR-12.7/45 |
10 |
12.7 |
6.6 |
23.0 |
45.0 |
/ |
400 |
|
Y5WR-17/45 |
10 |
17 |
13.6 |
24.0 |
45.0 |
/ |
400 |
|
Y1.5W-0.28/1.3 |
0.22 |
0.28 |
0.24 |
0.6 |
1.3 |
/ |
75 |
Low Voltage |
Y1.5W-0.5/2.6 |
0.38 |
0.5 |
0.24 |
1.2 |
2.6 |
/ |
75 |
|
Note:Porcelain |
Model |
Nominal Voltage |
Rated Voltage Of Arrester |
The Wave Front Steepness Of The Shock Discharge |
DC 1mA Reference Voltage kV Not Less Than |
1.2/50 Impulse Discharge Voltage Not Greater Than |
Wavefront Impulse Discharge Voltage
kV Not Greater Than |
The Residual Voltage Under Nominal Discharge Current 8/20μs
kV Not Greater Than |
2000μs Square Wave Flow Capacity |
4/10μs Impulse Current Capacity |
Y5CS-7.6/27 |
6 |
7.6 |
63 |
16 |
35 |
43.8 |
27 |
75 |
25 |
Y5CZ-7.6/24 |
6 |
7.6 |
63 |
16 |
30 |
37.5 |
24 |
150 |
40 |
Y5CS-12.7/45 |
10 |
12.7 |
106 |
26 |
50 |
62.5 |
45 |
75 |
25 |
Y5CS-12.7/41 |
10 |
12.7 |
106 |
26 |
45 |
56.5 |
41 |
200 |
40 |
Y5CZ-42/124 |
35 |
42.0 |
343 |
82 |
134 |
168 |
124 |
200 |
40 |
Note:Porcelain Series Gap
Installation
(1) The nameplate should be checked before installation, and the system rated voltage of the arrester should be consistent with the system voltage of the installation point;
(2) Suspension installation or vertical installation can be adopted. If vertical installation is adopted, the arrester cannot be used as a load-bearing support insulator;
(3) The lead wire should not be too long to avoid affecting the protection effect, and should not be tightened to avoid unnecessary stress on the arrester.
Test