Customization: | Available |
---|---|
Type: | Power Source Arrester |
Structure: | Zinc Oxide Arrester |
Still deciding? Get samples of $ !
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the state-of-the-art Zinc Oxide Arrester from Beierbian Group Co., Ltd—an extraordinary breakthrough in lightning protection technology, specifically designed for 10kV power distribution systems. This cutting-edge device is a pinnacle of innovation, expertly crafted with a zinc oxide valve column. It is enhanced by the precision placement of upper and lower electrodes, all flawlessly encapsulated in premium silicone rubber. This sophisticated construction presents unmatched features:
With a specially engineered valve plate and optimized core parameters, this advanced device confidently tackles challenges such as arc grounding, PT resonance, and various operational overvoltages. It operates with unparalleled reliability, consistently performing under normal line voltage and enduring 2.5 to 3 times power frequency overvoltage. Its voltage withstand duration not only meets but exceeds international standards by 1 to 3 orders of magnitude, delivering unmatched safety and exceptional operational longevity, setting new benchmarks for protection and assurance.
Main Characteristics Of Jacket Materials And Product Usage Environment:
Item |
Unit |
Norm |
Shore Hardness A |
/ |
60 |
Tensile Strength |
mpa |
≥35 |
Breaking Elongation |
% |
≥250 |
Oxygen Index |
/ |
45 |
Resistivity |
Ω.m |
≥1×1013 |
Breakdown Strength |
MV/m |
≥25 |
Tracking |
kV |
4.5 |
Durability |
Not less than 20 years |
Working Environment:
Meticulously crafted for flawless functionality, the Polymeric Lightning Protection system excels both indoors and outdoors;
Innovatively engineered to ensure seamless operation at altitudes reaching an impressive 3000 meters;
Constructed to endure a vast spectrum of temperatures, ranging from a stark -40°C to a warm +60°C, adapting effortlessly to extreme conditions;
Expertly designed to harmonize with power supply frequencies that range from a steady 48Hz to a dynamic 62Hz, ensuring compatibility and efficiency;
Guarantees power frequency voltage between terminals stays within optimal limits, offering enduring and reliable performance;
Engineered to withstand seismic activities up to 8 degrees, maintaining robustness and reliability during earthquakes;
Purposefully designed to resist fierce outdoor wind speeds up to an impressive 35 meters per second, ensuring stability in high winds;
Note:
If your conditions exceed these parameters, our expert team is on hand to provide customized solutions tailored to your needs.
Main Technical Parameters
Model |
Nominal Voltage (rms) |
Rated Voltage Of Arrester (rms) |
Continuous Operating Voltage (rms) |
DC 1mA reference voltage |
The residual voltage under nominal discharge current |
Steep wave impact residual voltage |
2ms square wave flow capacity |
Operation Place |
YH5WS-3.8/17 |
3 |
3.8 |
2.0 |
7.5 |
17.0 |
19.6 |
100 |
Distribution Type |
YH5WS-5/15 |
3 |
5 |
4.0 |
7.5 |
15.0 |
17.3 |
150 |
|
YH5WS-7.6/30 |
6 |
7.6 |
4.0 |
15.0 |
15.0 |
34.5 |
100 |
|
YH5WS-10/30 |
6 |
10 |
8.0 |
15.0 |
30.0 |
34.6 |
150 |
|
YH5WS-12.7/50 |
10 |
12.7 |
10 |
26.0 |
50.0 |
57.5 |
100 |
|
YH5WS-16.5/50 |
10 |
16.5 |
12.7 |
26.0 |
50.0 |
57.5 |
100 |
|
YH5WS-17/50 |
10 |
17 |
13.6 |
26.0 |
50.0 |
57.5 |
150 |
|
YH5WS-17/45 |
10 |
17 |
13.6 |
25.0 |
45.0 |
/ |
250 |
|
YH10WS-17/45 |
10 |
17 |
13.6 |
25.0 |
45.0 |
/ |
400 |
|
YH5WZ-5/13.5 |
3 |
5 |
4.0 |
7.2 |
13.5 |
15.5 |
200 |
Power Station Type |
YH5WZ-7.6/27 |
6 |
7.6 |
4.0 |
14.4 |
27.0 |
31.0 |
150 |
|
YH5WZ-10/27 |
6 |
10 |
8.0 |
14.4 |
27.0 |
31.0 |
200 |
|
YH5WZ-42/134 |
35 |
42 |
23.4 |
73 |
134 |
154 |
150 |
|
YH5WZ-12.7/45 |
10 |
12.7 |
6.6 |
24.0 |
45.0 |
51.8 |
150 |
|
YH5WZ-16.5/45 |
10 |
16.5 |
13.2 |
24.0 |
45.0 |
51.8 |
150 |
|
YH5WZ-17/45 |
10 |
17 |
13.6 |
24.0 |
45.0 |
51.8 |
200 |
|
YH5WZ-51/134 |
35 |
51 |
40.8 |
73.0 |
134 |
154 |
400 |
|
YH10WZ-17/45 |
10 |
17 |
13.6 |
24.0 |
45.0 |
51.8 |
200 |
|
YH10WZ-51/134 |
35 |
51 |
40.8 |
73.0 |
134 |
154 |
400 |
|
YH5WR-5/13.5 |
3 |
5 |
4.0 |
7.2 |
13.5 |
/ |
400 |
Capacitive Type |
YH5WR-7.6/27 |
6 |
7.6 |
4.0 |
13.8 |
27.0 |
/ |
400 |
|
YH5WR-10/27 |
6 |
10 |
8.0 |
14.4 |
27.0 |
/ |
400 |
|
YH5WR-12.7/45 |
10 |
12.7 |
6.6 |
23.0 |
45.0 |
/ |
400 |
|
YH5WR 17/45 |
10 |
17 |
13.6 |
24.0 |
45.0 |
/ |
400 |
|
YH5WX-51/134 |
35 |
51 |
40.8 |
73 |
134.0 |
154 |
400 |
Line type |
YH1.5W-30/80 |
35 |
30 |
24 |
44 |
80.0 |
/ |
600 |
Neutral Type |
Note: Featuring a durable, resilient Polymeric construction for unrivaled longevity.
Model |
Nominal Voltage (rms) |
Rated Voltage Of Arrester (rms) |
Continuous Operating Voltage (rms) |
DC 1mA Reference Voltage |
The Residual Voltage Under Nominal Discharge Current |
Steep Wave Impact Residual Voltage |
2ms Square Wave Flow Capacity |
Operation Place |
Y5WS-5/15 |
3 |
5 |
4.0 |
7.5 |
15.0 |
17.3 |
150 |
Distribution Type |
Y5WS-7.6/30 |
6 |
7.6 |
4.0 |
15.0 |
15.0 |
34.5 |
100 |
|
Y5WS-10/30 |
6 |
10 |
8.0 |
15.0 |
30.0 |
34.6 |
150 |
|
Y5WS-12.7/50 |
10 |
12.7 |
10 |
26.0 |
50.0 |
57.5 |
100 |
|
Y5WS-16.5/50 |
10 |
16.5 |
12.7 |
26.0 |
50.0 |
57.5 |
100 |
|
Y5WS-17/50 |
10 |
17 |
13.6 |
26.0 |
50.0 |
57.5 |
150 |
|
Y5WZ-5/13.5 |
3 |
5 |
4.0 |
7.2 |
13.5 |
15.5 |
200 |
Power Station Type |
Y5WZ-7.6/27 |
6 |
7.6 |
4.0 |
14.4 |
27.0 |
31.0 |
150 |
|
Y5WZ-10/27 |
6 |
10 |
8.0 |
14.4 |
27.0 |
31.0 |
200 |
|
Y5WZ-42/134 |
35 |
42 |
23.4 |
73 |
134 |
154 |
150 |
|
Y5WZ-12.7/45 |
10 |
12.7 |
6.6 |
24.0 |
45.0 |
51.8 |
150 |
|
Y5WZ-16.5/45 |
10 |
16.5 |
13.2 |
24.0 |
45.0 |
51.8 |
150 |
|
Y5WZ-17/45 |
10 |
17 |
13.6 |
24.0 |
45.0 |
51.8 |
200 |
|
Y5WZ-51/134 |
35 |
51 |
40.8 |
73.0 |
134 |
154 |
400 |
|
Y5WR-5/13.5 |
3 |
5 |
4.0 |
7.2 |
13.5 |
/ |
400 |
Capacitive Type |
Y5WR-7.6/27 |
6 |
7.6 |
4.0 |
13.8 |
27.0 |
/ |
400 |
|
Y5WR-10/27 |
6 |
10 |
8.0 |
14.4 |
27.0 |
/ |
400 |
|
Y5WR-12.7/45 |
10 |
12.7 |
6.6 |
23.0 |
45.0 |
/ |
400 |
|
Y5WR-17/45 |
10 |
17 |
13.6 |
24.0 |
45.0 |
/ |
400 |
|
Y1.5W-0.28/1.3 |
0.22 |
0.28 |
0.24 |
0.6 |
1.3 |
/ |
75 |
Low Voltage |
Y1.5W-0.5/2.6 |
0.38 |
0.5 |
0.24 |
1.2 |
2.6 |
/ |
75 |
|
Note:Porcelain |
Model |
Nominal Voltage |
Rated Voltage Of Arrester |
The Wave Front Steepness Of The Shock Discharge |
DC 1mA Reference Voltage kV Not Less Than |
1.2/50 Impulse Discharge Voltage Not Greater Than |
Wavefront Impulse Discharge Voltage
kV Not Greater Than |
The Residual Voltage Under Nominal Discharge Current 8/20μs
kV Not Greater Than |
2000μs Square Wave Flow Capacity |
4/10μs Impulse Current Capacity |
Y5CS-7.6/27 |
6 |
7.6 |
63 |
16 |
35 |
43.8 |
27 |
75 |
25 |
Y5CZ-7.6/24 |
6 |
7.6 |
63 |
16 |
30 |
37.5 |
24 |
150 |
40 |
Y5CS-12.7/45 |
10 |
12.7 |
106 |
26 |
50 |
62.5 |
45 |
75 |
25 |
Y5CS-12.7/41 |
10 |
12.7 |
106 |
26 |
45 |
56.5 |
41 |
200 |
40 |
Y5CZ-42/124 |
35 |
42.0 |
343 |
82 |
134 |
168 |
124 |
200 |
40 |
Note: Incorporates advanced Porcelain Series Gap specifications for enhanced performance and reliability.
Installation
(1) Prior to installation, verify the nameplate to ensure the arrester's system rated voltage aligns perfectly with the system voltage at the site;
(2) Offers installation versatility with suspension or vertical options. Ensure, for vertical installations, that the arrester is not used as a load-bearing insulator;
(3) Carefully optimize lead wire length to maintain protection efficiency and reduce stress on the equipment.
Test