Customization: | Available |
---|---|
Breaking Capacity: | 12kv/24kv/40.5kv |
Type: | Current Fuse |
Still deciding? Get samples of US$ 30/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
(H) RW(F) series outdoor high voltage AC drop fuse (hereinafter referred to as "fuse") is meticulously crafted for outdoor overhead distribution systems with a rated frequency of 50Hz and a rated voltage of 10kV (12/15/35/40.5). This fuse is your reliable guardian against overloads and short circuit faults in power systems, safeguarding circuits and electrical equipment. Seamlessly connected in series during normal operations, the fuse remains under tension with a securely locked movable joint. Upon detecting a fault, the fault current activates the fuse, releasing the movable joint, rapidly disconnecting the fuse tube, and ensuring the circuit is safely interrupted. This vital safety mechanism protects your power lines and equipment. An advanced load type fuse, featuring an elastic contact and arc extinguishing cover, enables the efficient opening and closing of load currents within the power system, maximizing safety and functionality.
The fuse is designed to meet stringent technical standards, including GB / T 15166.3 - 2008 high voltage AC fuses - Part 3: injection fuses, and DL / T 640 - 1997 outdoor AC high voltage drop tested fuses and fuse links ordering technical conditions, ensuring reliability and peace of mind.
Working Environment:
Recommended ambient temperature range: -40°C to +40°C.
Stay within optimal conditions with a relative humidity: daily average not exceeding 95%, and monthly average not exceeding 90%.
Maintain performance integrity at altitudes not exceeding 3000 meters.
Designed to withstand outdoor challenges with wind speeds not surpassing 34 meters/second.
Ideal installation site: Ensure the area is free from fire, explosion hazards, chemical corrosive gases, and is well-ventilated for optimal operation.
Note: Should conditions exceed the normal use parameters, users are encouraged to negotiate with the company for tailored solutions.
Technical Parameters
Note: We offer customization options to meet specific user requirements, ensuring perfect integration with your systems.
Model |
Voltage |
Current |
Rated maximum
breaking current |
1min power frequency dry withstand
voltage |
1min power frequency wet withstand
voltage |
Rated lightning impulse withstand
voltage |
Opening and closing
load current |
XS-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
XS-15/100(200) |
15 |
||||||
PD-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
PD-15/100(200) |
15 |
||||||
(H)RW3-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW3-12/100(200) |
12 |
||||||
(H)RW4-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW4-12/100(200) |
12 |
||||||
(H)RW7-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW7-12/100(200) |
12 |
||||||
(H)RW10-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW10-12/100(200) |
12 |
||||||
(H)RW10-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW10-12F/100(200) |
12 |
||||||
(H)RW11-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
! |
(H)RW11-12/100(200) |
12 |
||||||
(H)RW11-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW11-12F/100(200) |
12 |
||||||
(H)RW12-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
45 |
30 |
105 |
/ |
(H)RW12-12/100(200) |
12 |
||||||
(H)RW12-15/100(200) |
15 |
||||||
(H)PRWG1-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)PRWG1-12F/100(200) |
12 |
||||||
(H)RW33-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW33-15/100(200) |
15 |
||||||
(H)RW5-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)RW10-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)PRWG2-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |