The ZW32-12 outdoor high voltage vacuum circuit breaker, fondly referred to as the 'circuit breaker,' stands as a remarkable outdoor distribution switchgear, meticulously designed for a rated voltage of 12kV and a solid three-phase AC of 50Hz. This versatile powerhouse is adept at managing the interruption and reconnection of load current, overload current, and short circuit current within power grids. It boasts cutting-edge overload and short circuit protective capabilities, seamlessly fulfilling control and measurement requisites while offering advanced remote control and monitoring functions. Its extensive application spans substations, industrial sites, and mining enterprise distribution systems, providing unmatched control and efficient operation—perfectly suited for environments demanding frequent operations.
Structural features:
Crafted with meticulous precision, the circuit breaker features a robust three-phase pillar dry design;
Engineered with a fully enclosed structure, it delivers superior sealing, remarkable moisture resistance, and exceptional anti-condensation properties, making it the premier choice for high-temperature and humid climates;
Employs cutting-edge vacuum arc extinguishing technology, ensuring outstanding insulation reliability;
Exhibits flawless opening and closing performance, guaranteeing safety with no risk of combustion or explosion;
Compact, lightweight, maintenance-free, and promises an impressive longevity;
Versatile operation with options for manual, electric, or remote control;
The operating mechanism is expertly sealed at the base of the switch box, effectively safeguarding against outdoor environmental corrosion;
Showcases a novel, simplistic design with a dynamic mechanism that ensures reliable performance, compact form, and an astounding service life of up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |