Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Presenting the ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker, the ultimate solution for modern outdoor distribution networks. Often referred to as the 'circuit breaker,' this premium switchgear is ingeniously designed for a 12kV rated voltage and a robust three-phase AC at 50Hz. This innovative circuit breaker is unparalleled in its ability to smoothly handle the interruption and reconnection of load current, overload current, and short circuit current within power grids. It showcases state-of-the-art overload and short circuit protective features, effortlessly fulfilling control and measurement demands while providing sophisticated remote control and monitoring capabilities. Its wide-ranging application extends to substations, industrial settings, and mining enterprise distribution systems, making it the quintessential choice for environments necessitating frequent operations. This ensures unrivaled control and efficiency, rendering it an essential asset for contemporary electrical infrastructures.
Structural Features:
Crafted with meticulous precision, the circuit breaker boasts a refined three-phase pillar dry design;
Ingeniously engineered with a fully enclosed structure, it delivers outstanding sealing, exceptional moisture resistance, and anti-condensation properties, making it ideal for high-temperature and humid environments;
Incorporates cutting-edge vacuum arc extinguishing technology, providing exceptional insulation reliability;
Delivers impeccable opening and closing performance, ensuring unparalleled safety with no risk of combustion or explosion;
Designed to be compact and lightweight, this sophisticated device is maintenance-free, boasting an impressive lifespan;
Offers versatile operation capabilities, with manual, electric, or remote control options available for maximum convenience;
The operating mechanism is meticulously sealed at the base of the switch box, providing effective protection against outdoor environmental corrosion;
Showcases an innovative and streamlined design with a restless mechanism, ensuring reliable dynamic performance and a compact structure, along with an astonishing service life reaching up to 10,000 cycles.
Main Technical Parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |