Introducing the ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker, a true testament to innovation and reliability in modern distribution switchgear. Operating seamlessly at a rated voltage of 12kV, it harnesses the power of a robust three-phase AC at 50Hz. This circuit breaker excels at managing load current, overloads, and short circuits with unmatched precision. Engineered with advanced protective capabilities for overload and short circuits, it fulfills control and measurement needs, all while offering sophisticated remote control and monitoring features. Its versatility makes it an indispensable choice for substations, industrial facilities, and mining enterprise distribution systems, guaranteeing exceptional control and performance, particularly in environments demanding frequent operations.
Structural features:
Exquisitely engineered with a three-phase pillar dry design, the circuit breaker embodies precision craftsmanship;
Encased in a fully enclosed structure, it excels in sealing, moisture resistance, and anti-condensation capabilities, ideal for high-temperature, humid climates;
Utilizes cutting-edge vacuum arc extinguishing technology for remarkable insulation reliability;
Ensures impeccable opening and closing performance, offering ultimate safety with zero combustion or explosion risks;
Its compact, lightweight design requires no maintenance, guaranteeing an exceptional lifespan;
Flexible operation options include manual, electric, or remote control for utmost convenience;
With a meticulously sealed operating mechanism at the switch box base, it is well-protected from environmental corrosion;
Features a novel, simplistic design with a restless mechanism ensuring reliable dynamic performance and a compact form, boasting an incredible service life of up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |