Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The ZW32-12 outdoor high voltage vacuum circuit breaker, affectionately referred to as the 'circuit breaker,' is a premier outdoor distribution switchgear. It operates seamlessly at a rated voltage of 12kV with a formidable three-phase AC of 50Hz. This exceptional circuit breaker expertly manages the interruption and connection of load currents, overload currents, and short circuit currents within the power grid. It is designed with cutting-edge overload and short circuit protective capabilities, effortlessly meeting control and measurement requirements while offering sophisticated remote control and monitoring functionalities. Widely utilized in substations, industrial areas, and mining enterprise distribution systems, it delivers unmatched control and operational excellence, making it ideal for environments that demand frequent operations.
Structural features:
Crafted with precision, this circuit breaker features a robust three-phase pillar dry design, engineered for reliability;
Designed with a fully enclosed structure, it offers superior sealing, exceptional moisture resistance, and anti-condensation properties, making it the ideal choice for high-temperature and humid regions;
Incorporates state-of-the-art vacuum arc extinguishing technology, providing outstanding insulation reliability;
Delivers impeccable opening and closing performance, ensuring safety with no risk of combustion or explosion;
Compact and lightweight, requiring no maintenance, and offers an impressive lifespan;
Versatility in operation, with manual, electric, or remote control options available;
The meticulously sealed operating mechanism at the base of the switch box effectively protects against outdoor environmental corrosion;
Showcases a novel, simplistic design with a restless mechanism that ensures reliable dynamic performance, compact form, and an astounding service life of up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |