Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 outdoor high voltage vacuum circuit breaker, affectionately known as the 'circuit breaker.' This premium outdoor distribution switchgear is meticulously designed for performance at a rated voltage of 12kV, adeptly managing a robust three-phase AC of 50Hz. This dynamic circuit breaker masterfully facilitates the interruption and connection of load current, overload current, and short circuit current within the power grid. It is equipped with cutting-edge overload and short circuit protective capabilities, flawlessly meeting control and measurement specifications while providing sophisticated remote control and monitoring functionalities. Its extensive applications span substations, industrial realms, and mining enterprise distribution systems, where it delivers exceptional control and operation, making it the quintessential choice for environments demanding frequent operations.
Structural features:
This expertly crafted circuit breaker features a three-phase pillar dry design, displaying remarkable precision and engineering;
Engineered with a fully enclosed structure, this breaker offers unparalleled sealing capabilities, exceptional moisture resistance, and robust anti-condensation properties, making it the ultimate selection for high-temperature and humid regions;
Utilizes cutting-edge vacuum arc extinguishing technology, ensuring phenomenal insulation reliability;
Exhibits flawless opening and closing performance, ensuring utmost safety with zero risk of combustion or explosion, providing peace of mind to operators;
This compact and lightweight marvel demands no maintenance and promises an impressive, long-lasting lifespan, enhancing operational efficiency;
Offers versatility in operation with manual, electric, or remote control options, catering to diverse operational needs;
The operating mechanism is meticulously sealed at the base of the switch box, providing comprehensive protection against environmental corrosion, enhancing durability;
Boasts a novel, simplistic design with a restless mechanism, ensuring reliable dynamic performance, compact form, and an astonishing service life reaching up to 10,000 cycles, setting new standards in operational longevity.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |