The S-M series three-phase oil-immersed transformer adopts a fully oil-filled, sealed corrugated oil tank, boasting oil tank shells that naturally adapt to oil expansion while ensuring superior heat dissipation. It is renowned for its high efficiency and low loss characteristics.
This advanced transformer not only conserves substantial power and reduces operational expenses but also finds extensive application in power plants, substations, industrial and mining enterprises, as well as ports, airports, and various environmentally sensitive areas.
Standard: IEC60076-1, IEC60076-2, IEC60076-3, IEC60076-5, IEC60076-10: Built to meet and exceed international standards, ensuring ultimate quality and performance.
1. Ambient temperature: maximum temperature: +40°C, minimum temperature: -25ºC: Designed to withstand a broad range of temperatures, ensuring reliable performance in various climatic conditions.
2. Average temperature of the hottest month: +30ºC, average temperature in the hottest year: +20ºC: Adaptable to extreme heat conditions for sustained operation.
3. Altitude not exceeding 1000m: Engineered to perform optimally even at significant altitudes.
4. The waveform of the power supply voltage is similar to a sine wave: Ensures compatibility with standard power supply formats.
5. The three-phase supply voltage should be approximately symmetrical: Maintains balance and stability in power distribution.
6. The total harmonic content of the load current shall not exceed 5% of the rated current: Ensures clean and efficient power delivery without distortion.
7. Where to use: indoors or outdoors: Versatile for diverse applications, whether in controlled environments or exposed settings.
1. The product boasts high efficiency, low loss, and low noise, providing an ideal solution for energy-conscious users.
2. With high mechanical strength and balanced ampere-turn distribution, it offers robust resistance to short-circuits.
3. Experience minimal no-load and load loss, maximizing energy savings and operational efficiency.
4. Compact size, reliable operation, extended service life, and maintenance-free design make it a preferred choice for hassle-free performance.
Structure
Iron core:
Iron core:
The iron core is crafted from premium, high-performance, high-permeability silicon steel sheets, ensuring exceptionally low no-load losses.
High/low voltage winding:
The low-voltage winding of 500KVA and below features a layer type, while 630KVA and above utilize a new spiral type, providing optimal performance and durability.
It is characterized by high mechanical strength, balanced ampere-turn distribution, and robust short-circuit resistance, ensuring reliable operation under extreme conditions.
Fully sealed structure:
This product features a fully sealed structure, employing a vacuum oil filling process for the transformer packaging. This method completely eliminates moisture, secures the transformer oil's isolation from external air, prevents oil aging, and significantly enhances the transformer's operational reliability.
Positioning structure:
The product body incorporates a positioning structure to prevent displacement during transportation, with all fasteners designed to ensure stability and security.
Meticulously crafted with precision-engineered fastening nuts, this innovative design guarantees that the fasteners remain steadfast and secure, preventing any loosening throughout the enduring operational lifecycle of the product.
Oil Tank:
Our cutting-edge oil tank features a superior corrugated design, offering a streamlined process with exceptional mechanical strength. The advanced welding technique ensures a leak-proof construction, while the dynamic fluidity of the oil significantly enhances the product's heat dissipation capabilities.
Additional Configuration:
Expertly equipped with a state-of-the-art pressure relief valve and a precision signal thermometer, this configuration ensures the seamless and safe operation of the transformer.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Yzn11 |
130 | 630/600 | 2.3 | 4 | 745 | 530 | 890 | 280 |
50 | 170 | 910/870 | 2 | 790 | 560 | 940 | 365 | |||||
63 | 200 | 1090/1040 | 1.9 | 820 | 570 | 950 | 425 | |||||
80 | 250 | 1310/1250 | 1.9 | 850 | 580 | 1000 | 485 | |||||
100 | 290 | 1580/1500 | 1.8 | 900 | 620 | 1010 | 540 | |||||
125 | 340 | 1890/1800 | 1.7 | 880 | 630 | 1050 | 610 | |||||
160 | 400 | 2310/2200 | 1.6 | 950 | 690 | 1120 | 710 | |||||
200 | 480 | 2730/2600 | 1.5 | 990 | 730 | 1200 | 835 | |||||
250 | 560 | 3200/3050 | 1.4 | 1180 | 700 | 1200 | 970 | |||||
315 | 670 | 3830/3650 | 1.4 | 1230 | 760 | 1250 | 1125 | |||||
400 | 800 | 4520/4300 | 1.3 | 1260 | 800 | 1300 | 1310 | |||||
500 | 960 | 5410/5150 | 1.2 | 1400 | 900 | 1320 | 1530 | |||||
630 | Dyn11 Yyn0 Yzn11 |
1200 | 6200 | 1.1 | 4.5 | 1530 | 940 | 1350 | 1890 | |||
800 | 1400 | 7500 | 1 | 1580 | 1000 | 1420 | 2185 | |||||
1000 | 1700 | 10300 | 1 | 1770 | 1180 | 1450 | 2480 | |||||
1250 | 1950 | 12000 | 0.9 | 1920 | 1290 | 1430 | 3020 | |||||
1600 | 2400 | 14500 | 0.8 | 1990 | 1340 | 1620 | 3550 | |||||
2000 | 3000 | 17100 | 0.7 | 5 | 1950 | 1680 | 2100 | 4530 | ||||
2500 | 3300 | 23200 | 0.7 | 2020 | 1710 | 2100 | 5030 |
Note 1: For transformers with a rated capacity of 500kVA or below, the specified load loss values positioned above the diagonal line in the table are relevant for the Dyn11 or Yzn11 coupling groups. Meanwhile, values below the diagonal line apply to the Yyn0 coupling group.
Note 2: To achieve the pinnacle of operational efficiency, when the transformer's average annual load rate falls between 35% and 40%, utilize the specified loss values in the table.
Overall and Mounting Dimensions (mm)
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Yzn11 |
100 | 630/600 | 1.5 | 4 | 690 | 510 | 920 | 275 |
50 | 130 | 910/870 | 1.3 | 730 | 510 | 960 | 340 | |||||
63 | 150 | 1090/1040 | 1.2 | 750 | 550 | 1000 | 385 | |||||
80 | 180 | 1310/1250 | 1.2 | 790 | 620 | 1020 | 450 | |||||
100 | 200 | 1580/1500 | 1.1 | 790 | 700 | 1040 | 520 | |||||
125 | 240 | 1890/1800 | 1.1 | 840 | 800 | 1070 | 625 | |||||
160 | 280 | 2310/2200 | 1 | 1070 | 670 | 1130 | 695 | |||||
200 | 340 | 2730/2600 | 1 | 1140 | 750 | 1140 | 795 | |||||
250 | 400 | 3200/3050 | 0.9 | 1200 | 800 | 1190 | 955 | |||||
315 | 480 | 3830/3650 | 0.9 | 1300 | 860 | 1210 | 1085 | |||||
400 | 570 | 4520/4300 | 0.8 | 1380 | 900 | 1240 | 1290 | |||||
500 | 680 | 5410/5100 | 0.8 | 1450 | 950 | 1300 | 1590 | |||||
630 | Dyn11 Yyn0 Yzn11 |
810 | 6200 | 0.6 | 4.5 | 1500 | 970 | 1360 | 1850 | |||
800 | 980 | 7500 | 0.6 | 1660 | 1140 | 1400 | 2210 | |||||
1000 | 1150 | 10300 | 0.6 | 1690 | 1190 | 1530 | 2570 | |||||
1250 | 1360 | 12000 | 0.5 | 1760 | 1230 | 1600 | 3115 | |||||
1600 | 1640 | 14500 | 0.5 | 1800 | 1250 | 1660 | 3520 | |||||
2000 | 1940 | 18300 | 0.4 | 5 | 1930 | 1360 | 1490 | 4060 | ||||
2500 | 2290 | 21200 | 0.4 | 2080 | 1360 | 1570 | 5105 |
Note 1: For transformers with a rated capacity of 500kVA or below, the load loss values above the diagonal line in the table are applicable to the Dyn11 or Yzn11 coupling group, while those below are relevant to the Yyn0 coupling group.
Note 2: Optimal efficiency is achieved when the transformer's average annual load rate is between 35% and 40%, by adhering to the specified loss values in the table.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Yzn11 |
80 | 630/600 | 1.5 | 4 | 685 | 490 | 860 | 260 |
50 | 100 | 910/870 | 1.3 | 725 | 520 | 955 | 365 | |||||
63 | 110 | 1090/1040 | 1.2 | 750 | 535 | 970 | 415 | |||||
80 | 130 | 1310/1250 | 1.2 | 770 | 565 | 985 | 465 | |||||
100 | 150 | 1580/1500 | 1.2 | 800 | 595 | 1000 | 545 | |||||
125 | 170 | 1890/1800 | 1.1 | 815 | 670 | 1010 | 585 | |||||
160 | 200 | 2310/2200 | 1.1 | 1015 | 645 | 1055 | 695 | |||||
200 | 240 | 2730/2600 | 1 | 1020 | 650 | 1115 | 810 | |||||
250 | 290 | 3200/3050 | 1 | 1140 | 730 | 1120 | 930 | |||||
315 | 340 | 3830/3650 | 0.9 | 1195 | 785 | 1175 | 1075 | |||||
400 | 410 | 4520/4300 | 0.9 | 1265 | 855 | 1195 | 1255 | |||||
500 | 480 | 5410/5100 | 0.8 | 1325 | 915 | 1240 | 1435 | |||||
630 | Dyn11 Yyn0 Yzn11 |
570 | 6200 | 0.8 | 4.5 | 1465 | 960 | 1295 | 1880 | |||
800 | 700 | 7500 | 0.6 | 1515 | 995 | 1340 | 2145 | |||||
1000 | 830 | 10300 | 0.6 | 1605 | 1095 | 1460 | 2455 | |||||
1250 | 970 | 12000 | 0.5 | 1685 | 1145 | 1485 | 2840 | |||||
1600 | 1170 | 14500 | 0.5 | 1775 | 1225 | 1580 | 3310 | |||||
2000 | 1550 | 18300 | 0.4 | 5 | 1855 | 1265 | 1600 | 3960 | ||||
2500 | 1830 | 21200 | 0.4 | 1885 | 1305 | 1780 | 4980 |
Note 1: For transformers with rated capacities of 500kVA and below, the load loss values specified above the diagonal line pertain to the Dyn11 or Yzn11 coupling group. Values below pertain to the Yyn0 coupling group.
Note 2: The maximum operational efficiency is realized when the transformer's average annual load rate ranges from 35% to 40%, using the values specified in the table.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Yzn11 |
80 | 505/480 | 1.5 | 4 | 785 | 710 | 880 | 370 |
50 | 100 | 730/695 | 1.3 | 800 | 730 | 940 | 480 | |||||
63 | 110 | 870/830 | 1.2 | 815 | 720 | 970 | 535 | |||||
80 | 130 | 1050/1000 | 1.2 | 830 | 740 | 990 | 580 | |||||
100 | 150 | 1260/1200 | 1.1 | 875 | 790 | 1010 | 705 | |||||
125 | 170 | 1510/1440 | 1.1 | 875 | 770 | 1050 | 775 | |||||
160 | 200 | 1850/1760 | 1 | 935 | 820 | 1140 | 975 | |||||
200 | 240 | 2180/2080 | 1 | 995 | 870 | 1140 | 1140 | |||||
250 | 290 | 2560/2440 | 0.9 | 995 | 900 | 1180 | 1240 | |||||
315 | 340 | 3060/2920 | 0.9 | 1030 | 880 | 1250 | 1425 | |||||
400 | 410 | 3610/3440 | 0.8 | 1075 | 910 | 1270 | 1635 | |||||
500 | 480 | 4330/4120 | 0.8 | 1120 | 930 | 1320 | 1950 | |||||
630 | Dyn11 Yyn0 Yzn11 |
570 | 4960 | 0.6 | 4.5 | 1165 | 950 | 1350 | 2150 | |||
800 | 700 | 6000 | 0.6 | 1210 | 1050 | 1390 | 2515 | |||||
1000 | 830 | 8240 | 0.6 | 1520 | 1020 | 1450 | 2635 | |||||
1250 | 970 | 9600 | 0.5 | 1630 | 1090 | 1540 | 3210 | |||||
1600 | 1170 | 11600 | 0.5 | 1680 | 1150 | 1600 | 3905 | |||||
2000 | 1550 | 14600 | 0.4 | 5 | 1890 | 1300 | 1600 | 4130 | ||||
2500 | 1830 | 16900 | 0.4 | 1990 | 1360 | 1700 | 5250 |
Note 1: For transformers with a rated capacity of 500kVA and below, load loss values above the diagonal apply to Dyn11 or Yzn11 coupling groups, while those below apply to the Yyn0 group.
Note 2: Achieve peak efficiency by using specified loss values, particularly when the transformer’s average annual load rate is between 35% and 40%.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Dyn5 |
70 | 505 | 1.2 | 4 | 785 | 710 | 880 | / |
50 | 90 | 730 | 1.04 | 800 | 730 | 940 | / | |||||
80 | 115 | 1050 | 0.96 | 830 | 740 | 990 | / | |||||
100 | 135 | 1265 | 0.88 | 875 | 790 | 1010 | / | |||||
125 | 150 | 1510 | 0.88 | 875 | 770 | 1050 | / | |||||
160 | 180 | 1850 | 0.8 | 935 | 820 | 1140 | / | |||||
200 | 215 | 2185 | 0.8 | 995 | 870 | 1140 | / | |||||
250 | 260 | 2560 | 0.72 | 995 | 900 | 1180 | / | |||||
315 | 305 | 3065 | 0.72 | 1030 | 880 | 1250 | / | |||||
400 | 370 | 3615 | 0.64 | 1075 | 910 | 1270 | / | |||||
500 | 430 | 4330 | 0.64 | 1120 | 930 | 1320 | / | |||||
630 | 510 | 4960 | 0.48 | 4.5 | 1165 | 950 | 1350 | / | ||||
800 | 630 | 6000 | 0.48 | 1210 | 1050 | 1390 | / | |||||
1000 | 745 | 8240 | 0.48 | 1520 | 1020 | 1450 | / | |||||
1250 | 870 | 9600 | 0.4 | 1630 | 1090 | 1540 | / | |||||
1600 | 1050 | 11600 | 0.4 | 1680 | 1150 | 1600 | / | |||||
2000 | 1225 | 14640 | 0.32 | 5 | 1890 | 1300 | 1600 | / | ||||
2500 | 1440 | 14840 | 0.32 | 1990 | 1360 | 1700 | / |
Note 1: For transformers rated at 500kVA and lower, the load loss values seen above the diagonal line are for Dyn11 or Yzn11, and those below for Yyn0 coupling group.
Note 2: To maximize efficiency, particularly when the average annual load rate sits between 35% and 40%, rely on the table's loss values.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Dyn5 |
65 | 455 | 1.2 | 4 | 785 | 710 | 880 | / |
50 | 80 | 655 | 1.04 | 800 | 730 | 940 | / | |||||
80 | 105 | 945 | 0.96 | 830 | 740 | 990 | / | |||||
100 | 120 | 1140 | 0.88 | 875 | 790 | 1010 | / | |||||
125 | 135 | 1360 | 0.88 | 875 | 770 | 1050 | / | |||||
160 | 160 | 1665 | 0.8 | 935 | 820 | 1140 | / | |||||
200 | 190 | 1970 | 0.8 | 995 | 870 | 1140 | / | |||||
250 | 230 | 2300 | 0.72 | 995 | 900 | 1180 | / | |||||
315 | 270 | 2760 | 0.72 | 1030 | 880 | 1250 | / | |||||
400 | 330 | 3250 | 0.64 | 1075 | 910 | 1270 | / | |||||
500 | 385 | 3900 | 0.64 | 1120 | 930 | 1320 | / | |||||
630 | 460 | 4460 | 0.48 | 4.5 | 1165 | 950 | 1350 | / | ||||
800 | 560 | 5400 | 0.48 | 1210 | 1050 | 1390 | / | |||||
1000 | 665 | 7415 | 0.48 | 1520 | 1020 | 1450 | / | |||||
1250 | 780 | 8640 | 0.4 | 1630 | 1090 | 1540 | / | |||||
1600 | 940 | 10440 | 0.4 | 1680 | 1150 | 1600 | / | |||||
2000 | 1085 | 13180 | 0.32 | 5 | 1890 | 1300 | 1600 | / | ||||
2500 | 1280 | 13360 | 0.32 | 1990 | 1360 | 1700 | / |
Note 1: For transformers boasting a rated capacity of 500kVA and below, the table's diagonal line serves as a guide. Above this line, Dyn11 or Yzn11 coupling groups find their load loss values, while below, the Yyn0 coupling group claims its territory.
Note 2: For those seeking peak performance, when the transformer's average annual load rate ranges between 35% and 40%, optimal efficiency awaits by adhering to the table's specified loss values.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
25 | 20 10 6 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Dyn5 |
63 | 600 | 1.7 | 5.5(20kV) 4 (6kV, 10kV) |
1090 | 600 | 1150 | / |
50 | 81 | 750 | 1.6 | 1120 | 620 | 1180 | / | |||||
100 | 130 | 1250 | 1.3 | 1150 | 650 | 1290 | / | |||||
160 | 189 | 1750 | 1.1 | 1160 | 675 | 1380 | / | |||||
250 | 270 | 2350 | 0.96 | 1200 | 880 | 1400 | / | |||||
315 | 324 | 2800 | 0.88 | 1230 | 920 | 1460 | / | |||||
400 | 387 | 3250 | 0.8 | 1250 | 950 | 1580 | / | |||||
500 | 459 | 3900 | 0.8 | 1390 | 960 | 1580 | / | |||||
630 | 540 | 4600 | 0.72 | 6(20kV) 4.5 (6kV, 10kV) |
1450 | 980 | 1600 | / | ||||
800 | 585 | 6000 | 0.64 | 1560 | 1020 | 1720 | / | |||||
1000 | 693 | 7600 | 0.56 | 1700 | 1070 | 1790 | / | |||||
1250 | 855 | 9500 | 0.56 | 1700 | 1070 | 1791 | / | |||||
1600 | 1080 | 12000 | 0.48 | 1850 | 1130 | 1850 | / | |||||
2000 | 1305 | 15000 | 0.48 | 6(20kV) 5 (6kV, 10kV) |
2000 | 1280 | 1980 | / | ||||
2500 | 1575 | 18500 | 0.4 | 2040 | 1320 | 2050 | / | |||||
3150 | 1980 | 23000 | 0.4 | 2200 | 1400 | 2250 | / |
Note 1: For transformers with rated capacity of 500kVA and below, the diagonal line within the table reveals its secrets. Above it, the Dyn11 or Yzn11 coupling group reigns with specific load loss values, while below, the Yyn0 coupling group finds its match.
Note 2: Unlock the potential for maximum operational efficiency! When the transformer's average annual load rate is nestled between 35% and 40%, the table's loss values guide the way to peak performance.