Customization: | Available |
---|---|
Breaking Capacity: | 12kv/24kv/40.5kv |
Type: | Current Fuse |
Still deciding? Get samples of US$ 30/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
(H) RW(F) series outdoor high voltage AC drop fuse, affectionately referred to as the 'fuse,' is expertly engineered for outdoor overhead distribution systems that operate with a rated frequency of 50Hz and a versatile range of rated voltages including 10kV (12/15/35/40.5). This dynamic protective element is indispensable for safeguarding circuits and electrical equipment, stepping in seamlessly during overloads or short circuit faults in power systems. Under normal conditions, the fuse maintains a series connection with the power line, held in a tensioned state with a securely locked movable joint. In the event of a line failure, the fault current triggers the fuse to blow, releasing the movable joint, swiftly dropping the fuse tube, and efficiently cutting off the circuit. This critical mechanism ensures unparalleled safety protection for line and equipment maintenance. The load type fuse is further enhanced with an elastic contact and an arc extinguishing cover, granting it the capability to adeptly open and close the load current within the power system.
The fuse adheres to stringent technical standards including GB / T 15166.3 - 2008 for high voltage AC fuses - Part 3: injection fuses, as well as DL / T 640 - 1997 pertaining to outdoor AC high voltage drop tested fuses and fuse links ordering technical conditions.
Working Environment:
Ambient temperature: Seamlessly operates between -40°C to +40°C;
Relative humidity: Maintains optimum performance with a daily average not exceeding 95% and a monthly average not more than 90%;
The altitude does not exceed 3000 meters, ensuring reliability across varied terrains;
Outdoor wind speed capabilities extend up to 34 meters/second, proving its resilience in diverse weather conditions;
Installation site: Designed for spaces devoid of fire, explosion hazards, chemical corrosive gases, and ensures excellent ventilation.
Note: For conditions that exceed the specified normal usage, customized negotiations with the company are available.
Technical parameters
Note: Our company offers the flexibility to supply products tailored to specific user requirements.
Model |
Voltage |
Current |
Rated maximum
breaking current |
1min power frequency dry withstand
voltage |
1min power frequency wet withstand
voltage |
Rated lightning impulse withstand
voltage |
Opening and closing
load current |
XS-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
XS-15/100(200) |
15 |
||||||
PD-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
PD-15/100(200) |
15 |
||||||
(H)RW3-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW3-12/100(200) |
12 |
||||||
(H)RW4-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW4-12/100(200) |
12 |
||||||
(H)RW7-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW7-12/100(200) |
12 |
||||||
(H)RW10-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW10-12/100(200) |
12 |
||||||
(H)RW10-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW10-12F/100(200) |
12 |
||||||
(H)RW11-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
! |
(H)RW11-12/100(200) |
12 |
||||||
(H)RW11-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW11-12F/100(200) |
12 |
||||||
(H)RW12-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
45 |
30 |
105 |
/ |
(H)RW12-12/100(200) |
12 |
||||||
(H)RW12-15/100(200) |
15 |
||||||
(H)PRWG1-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)PRWG1-12F/100(200) |
12 |
||||||
(H)RW33-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW33-15/100(200) |
15 |
||||||
(H)RW5-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)RW10-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)PRWG2-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |