Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 outdoor high voltage vacuum circuit breaker, fondly referred to as the 'circuit breaker,' which stands as a pinnacle of outdoor distribution switchgear innovation. Skillfully crafted for operation at a rated voltage of 12kV, this dynamic solution features a robust three-phase AC of 50Hz. It adeptly manages the interruption and connection of load current, overload current, and short circuit current within the power grid. With advanced overload and short circuit protective capabilities, it seamlessly meets control and measurement demands, all while offering sophisticated remote control and monitoring functionalities. It's an optimal choice for substations, industrial settings, and mining enterprise distribution systems, delivering exceptional control and operation—perfectly suited for environments demanding frequent operations.
Structural features:
Impeccably designed, the circuit breaker flaunts a refined three-phase pillar dry architecture;
Built with a fully enclosed structure, it offers unmatched sealing, superior moisture resistance, and anti-condensation attributes. This makes it a prime choice for high-temperature and humid climates;
Utilizes cutting-edge vacuum arc extinguishing technology, ensuring remarkable insulation reliability;
Provides flawless opening and closing performance, guaranteeing safety with no combustion or explosion risk;
Compact and lightweight, requiring zero maintenance, and promises a remarkable lifespan of dependability;
Offers operational versatility with manual, electric, or remote control capabilities;
The operating mechanism is expertly sealed at the switch box base, safeguarding it against the corrosive outdoor environment;
Exhibits a groundbreaking, minimalist design with a restless mechanism that ensures dynamic performance reliability, compactness, and an astounding service life extending up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |