Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The ZW32-12 outdoor high voltage vacuum circuit breaker, affectionately known as the 'circuit breaker,' is a state-of-the-art outdoor distribution switchgear tailored to operate seamlessly at a rated voltage of 12kV, supported by a robust three-phase AC frequency of 50Hz. This exquisite circuit breaker is designed to masterfully handle the interruption and connection of load current, overload current, and short circuit current within the power grid. It boasts sophisticated advanced overload and short circuit protective capabilities, harmoniously fulfilling control and measurement specifications while delivering cutting-edge remote control and monitoring functionalities. Its broad usage extends across substations, industrial settings, and mining enterprise distribution systems, providing unmatched control and operation—ideal for environments with frequent operations, making it an indispensable asset in modern power distribution.
Structural features:
Crafted with meticulous precision, the circuit breaker showcases a robust three-phase pillar dry design, embodying engineering excellence;
Engineered with a fully enclosed structure, it offers superior sealing, exceptional moisture resistance, and anti-condensation properties, rendering it the ideal choice for high-temperature and humid regions, ensuring enduring performance;
Employs state-of-the-art vacuum arc extinguishing technology, delivering outstanding insulation reliability and ensuring safety;
Delivers flawless opening and closing performance, ensuring unparalleled safety with no risk of combustion or explosion, setting a new standard in operational security;
Compact and lightweight, requiring no maintenance, this circuit breaker promises an impressive lifespan, guaranteeing enduring utility;
Versatility in operation—offering manual, electric, or remote control options—catering to diverse user requirements;
The operating mechanism is meticulously sealed at the base of the switch box, effectively safeguarding it against the harsh outdoor environmental corrosion, ensuring longevity;
Showcases a novel, simplistic design with a restless mechanism that ensures exceptional reliable dynamic performance, compact form, and an astounding service life of up to 10,000 cycles, redefining durability.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |