Introducing the ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker, fondly referred to as the 'circuit breaker.' This outstanding piece of outdoor distribution switchgear is designed to excel at a rated voltage of 12kV, paired with a robust three-phase AC of 50Hz. Its versatility shines as it adeptly manages the interruption and connection of load current, overload current, and the formidable short circuit current within the power grid. Celebrated for its advanced overload and short circuit protective capabilities, this circuit breaker not only meets but surpasses control and measurement specifications. It goes beyond traditional functionalities by offering advanced remote control and monitoring capabilities. Its exceptional utility spreads across substations, various industrial settings, and the intricate distribution systems of mining enterprises, ensuring unparalleled control and operation. Ideal for environments with frequent operations, this circuit breaker is the epitome of innovation and reliability.
Structural features:
Meticulously crafted, the circuit breaker flaunts a three-phase pillar dry design, showcasing expert precision and engineering.
Engineered to perfection with a fully enclosed structure, it ensures superior sealing, along with exceptional moisture resistance and anti-condensation properties, rendering it the ideal choice for high-temperature and humid regions.
Incorporates cutting-edge vacuum arc extinguishing technology, delivering outstanding insulation reliability that sets industry standards.
Boasting flawless opening and closing performance, it guarantees safety with zero risk of combustion or explosion, prioritizing security and peace of mind.
Designed to be compact and lightweight, this circuit breaker requires no maintenance, promising a remarkable lifespan unmatched by its peers.
Offers versatility in operation with manual, electric, or remote control options, catering to a wide range of operational preferences.
The operating mechanism is expertly sealed at the base of the switch box, offering robust protection against environmental corrosion, thus enhancing longevity and performance.
Featuring a novel and simplistic design, it integrates a restless mechanism that ensures reliable dynamic performance, a compact form factor, and an astounding service life reaching up to 10,000 cycles, redefining durability.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |