Customization: | Available |
---|---|
Breaking Capacity: | 12kv/24kv/40.5kv |
Type: | Current Fuse |
Still deciding? Get samples of US$ 30/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
(H) RW(F) series outdoor high voltage AC drop fuse (hereinafter referred to as "fuse") is applicable to the outdoor overhead distribution systems with a rated frequency of 50Hz and rated voltage of 10kV(12/15/35/40.5). It is used as a protective element of circuit or electrical equipment in case of overload or short circuit fault of a power system. When traveling normally, the fuse is connected in series in the power line, the fuse is in a tensioned state, and the movable joint is locked. When the line fails, the fault current causes the fuse to blow, the movable joint is released, the fuse tube is quickly dropped, and the circuit is cut off, which plays a role in safety protection for the maintenance of the line and equipment. The load type fuse is added with elastic contact and arc extinguishing cover on the basis of the ordinary type, which is used to open and close the load current in the power system.
The fuse shall comply with technical standards such as GB / T 15166.3 - 2008 high voltage AC fuses - Part 3: injection fuses, DL / T 640 - 1997 outdoor AC high voltage drop tested fuses and fuse links ordering technical conditions.
Working Environment:
Ambient temperature: -40C +40C;
Relative humidity: the daily average is not more than 95%, and the monthly average is not more than 90%;
The altitude does not exceed 3000m;
Outdoor wind speed not exceeding 34 meters/second;
Installation site: no fire, explosion hazard, chemical corrosive gas and well-ventilated place.
Note: When the above normal use conditions are exceeded, the user can negotiate with the company.
echnical parameters
Note: Our company can supply products according to user requirements.
Model |
Voltage |
Current |
Rated maximum
breaking current |
1min power frequency dry withstand
voltage |
1min power frequency wet withstand
voltage |
Rated lightning impulse withstand
voltage |
Opening and closing
load current |
XS-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
XS-15/100(200) |
15 |
||||||
PD-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
PD-15/100(200) |
15 |
||||||
(H)RW3-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW3-12/100(200) |
12 |
||||||
(H)RW4-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW4-12/100(200) |
12 |
||||||
(H)RW7-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW7-12/100(200) |
12 |
||||||
(H)RW10-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW10-12/100(200) |
12 |
||||||
(H)RW10-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW10-12F/100(200) |
12 |
||||||
(H)RW11-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
! |
(H)RW11-12/100(200) |
12 |
||||||
(H)RW11-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW11-12F/100(200) |
12 |
||||||
(H)RW12-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
45 |
30 |
105 |
/ |
(H)RW12-12/100(200) |
12 |
||||||
(H)RW12-15/100(200) |
15 |
||||||
(H)PRWG1-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)PRWG1-12F/100(200) |
12 |
||||||
(H)RW33-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW33-15/100(200) |
15 |
||||||
(H)RW5-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)RW10-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)PRWG2-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |