Customization: | Available |
---|---|
Breaking Capacity: | 12kv/24kv/40.5kv |
Type: | Current Fuse |
Still deciding? Get samples of US$ 30/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
(H) RW(F) Series Outdoor High Voltage AC Drop Fuse: This sophisticated fuse is engineered for outdoor overhead distribution systems, boasting a rated frequency of 50Hz and a rated voltage of 10kV (options available at 12/15/35/40.5). This essential component provides robust protection for circuits and electrical equipment, ensuring safety during overloads or short circuit faults in power systems. Under normal circumstances, the fuse is integrated into the power line in a tensioned state with a secured movable joint. In the event of a line fault, the fault current activates the fuse, releasing the movable joint and swiftly dropping the fuse tube to sever the circuit. This action safeguards the line and equipment maintenance. Enhanced with elastic contact and an arc extinguishing cover, the load type fuse adeptly manages the opening and closing of load currents within the power system.
Built to meet rigorous standards, the fuse aligns with technical specifications including GB / T 15166.3 - 2008 high voltage AC fuses - Part 3: injection fuses, and DL / T 640 - 1997 standards for outdoor AC high voltage drop tested fuses and fuse links ordering technical conditions.
Working Environment:
Ambient temperature: Ranges from -40°C to +40°C;
Relative Humidity: Maintains a daily average not exceeding 95%, and a monthly average below 90%;
Altitude: Maximum installation height is 3000 meters;
Wind Conditions: Suitable for areas where outdoor wind speeds do not surpass 34 meters/second;
Installation Site: Ideal for locations free of fire or explosion hazards, chemical corrosive gases, and must be well-ventilated.
Note: Should your conditions exceed these standards, we welcome discussions for tailored accommodations.
Technical Parameters
Note: Our company is fully capable of providing customized products to meet user-specific requirements.
Model |
Voltage |
Current |
Rated maximum
breaking current |
1min power frequency dry withstand
voltage |
1min power frequency wet withstand
voltage |
Rated lightning impulse withstand
voltage |
Opening and closing
load current |
XS-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
XS-15/100(200) |
15 |
||||||
PD-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
PD-15/100(200) |
15 |
||||||
(H)RW3-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW3-12/100(200) |
12 |
||||||
(H)RW4-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW4-12/100(200) |
12 |
||||||
(H)RW7-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW7-12/100(200) |
12 |
||||||
(H)RW10-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW10-12/100(200) |
12 |
||||||
(H)RW10-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW10-12F/100(200) |
12 |
||||||
(H)RW11-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
! |
(H)RW11-12/100(200) |
12 |
||||||
(H)RW11-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW11-12F/100(200) |
12 |
||||||
(H)RW12-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
45 |
30 |
105 |
/ |
(H)RW12-12/100(200) |
12 |
||||||
(H)RW12-15/100(200) |
15 |
||||||
(H)PRWG1-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)PRWG1-12F/100(200) |
12 |
||||||
(H)RW33-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW33-15/100(200) |
15 |
||||||
(H)RW5-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)RW10-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)PRWG2-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |