Customization: | Available |
---|---|
Breaking Capacity: | 12kv/24kv/40.5kv |
Type: | Current Fuse |
Still deciding? Get samples of US$ 30/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
(H) RW(F) series outdoor high voltage AC drop fuse stands at the forefront of modern electrical system design. It is the ideal, cutting-edge solution for outdoor overhead distribution networks, boasting a frequency of 50Hz and a remarkable voltage range spanning 10kV (12/15/35/40.5). This fuse plays a pivotal role in safeguarding circuits and electrical equipment from the perils of overloads or short-circuits within power systems. In its normal state, the fuse remains tightly tensioned and locked within the power line, guaranteeing uninterrupted connectivity. Should a fault arise, the intelligent design ensures that the fault current will cause the fuse to blow, thereby initiating the release of the movable joint. This rapid response results in the swift dropping of the fuse tube, effectively interrupting the circuit, and providing indispensable safety protection during maintenance efforts. Enhanced with an elastic contact and an arc extinguishing cover, this load type fuse excels at efficiently opening and closing the load current within the power system.
Precision-engineered to adhere to strict technical standards, our fuse aligns with GB / T 15166.3 - 2008 for high voltage AC fuses, Part 3: injection fuses, and DL / T 640 - 1997 for outdoor AC high voltage drop-tested fuses. These exemplary standards ensure unmatched performance and reliability under specified technical conditions.
Working Environment:
Crafted to endure a broad ambient temperature range from a brisk -40°C to a balmy +40°C, this product promises resilient performance across diverse climate conditions.
With a relative humidity tolerance ensuring that the daily average remains below 95% and the monthly average under 90%, this fuse is meticulously built to excel in high humidity environments.
Designed for use at altitudes not exceeding 3000 meters, our fuse is versatile enough to accommodate an array of geographical locations.
Skillfully engineered to withstand outdoor wind speeds reaching up to 34 meters per second, this fuse retains its stability and operational functionality even in challenging windy conditions.
Installation sites must be devoid of fire and explosion hazards as well as chemical corrosive gases, with ample ventilation, to ensure peak performance and safety.
Note: Should your conditions of use surpass the normal specifications, we encourage discussions with our team to tailor solutions that maintain both safety and efficiency.
Technical parameters
Note: We provide customizable solutions, expertly tailoring products to meet the distinct needs and specifications of our users.
Model |
Voltage |
Current |
Rated maximum
breaking current |
1min power frequency dry withstand
voltage |
1min power frequency wet withstand
voltage |
Rated lightning impulse withstand
voltage |
Opening and closing
load current |
XS-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
XS-15/100(200) |
15 |
||||||
PD-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
PD-15/100(200) |
15 |
||||||
(H)RW3-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW3-12/100(200) |
12 |
||||||
(H)RW4-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW4-12/100(200) |
12 |
||||||
(H)RW7-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW7-12/100(200) |
12 |
||||||
(H)RW10-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW10-12/100(200) |
12 |
||||||
(H)RW10-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW10-12F/100(200) |
12 |
||||||
(H)RW11-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
! |
(H)RW11-12/100(200) |
12 |
||||||
(H)RW11-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW11-12F/100(200) |
12 |
||||||
(H)RW12-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
45 |
30 |
105 |
/ |
(H)RW12-12/100(200) |
12 |
||||||
(H)RW12-15/100(200) |
15 |
||||||
(H)PRWG1-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)PRWG1-12F/100(200) |
12 |
||||||
(H)RW33-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW33-15/100(200) |
15 |
||||||
(H)RW5-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)RW10-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)PRWG2-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |