Customization: | Available |
---|---|
Breaking Capacity: | 12kv/24kv/40.5kv |
Type: | Current Fuse |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
(H) RW(F) series outdoor high voltage AC drop fuse, revered as the 'fuse', is engineered specifically for outdoor overhead distribution systems operating at a standard frequency of 50Hz and a rated voltage of 10kV (12/15/35/40.5). This sophisticated component acts as the guardian of circuits and electrical equipment, providing reliable protection against overloads or short circuits within power systems. Under normal operations, the fuse integrates seamlessly into the power line, where it remains tensioned and securely locked. However, when mishaps occur, the fault current energizes the fuse to blow, releasing the movable joint. This action swiftly drops the fuse tube, effectively severing the circuit and ensuring unparalleled safety for the preservation and maintenance of both line and equipment. Our load type fuse features added elastic contact and an arc extinguishing cover, elevating it beyond conventional types, and enabling it to proficiently open and close the load current in power systems.
This impeccable fuse is designed in full compliance with distinguished technical standards, including GB / T 15166.3 - 2008 for high voltage AC fuses, Part 3: injection fuses, and DL / T 640 - 1997 for outdoor AC high voltage drop tested fuses and fuse links ordering technical conditions.
Working Environment:
Ambient temperature: -40°C to +40°C;
Relative humidity: daily average does not surpass 95%, while the monthly average remains below 90%;
Designed for altitudes not exceeding a magnificent 3000m;
Capable of withstanding outdoor wind speeds up to 34 meters per second;
Installation site: requires a location devoid of fire, explosion hazards, and chemical corrosive gases, ensuring a well-ventilated environment.
Note: Should the normal usage conditions exceed the specified parameters, the user is encouraged to enter negotiations with the company for tailored solutions.
Technical parameters
Note: Our company stands ready to tailor product offerings to meet specific user requirements, ensuring satisfaction and fulfillment.
Model |
Voltage |
Current |
Rated maximum
breaking current |
1min power frequency dry withstand
voltage |
1min power frequency wet withstand
voltage |
Rated lightning impulse withstand
voltage |
Opening and closing
load current |
XS-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
XS-15/100(200) |
15 |
||||||
PD-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
PD-15/100(200) |
15 |
||||||
(H)RW3-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW3-12/100(200) |
12 |
||||||
(H)RW4-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW4-12/100(200) |
12 |
||||||
(H)RW7-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW7-12/100(200) |
12 |
||||||
(H)RW10-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW10-12/100(200) |
12 |
||||||
(H)RW10-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW10-12F/100(200) |
12 |
||||||
(H)RW11-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
! |
(H)RW11-12/100(200) |
12 |
||||||
(H)RW11-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW11-12F/100(200) |
12 |
||||||
(H)RW12-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
45 |
30 |
105 |
/ |
(H)RW12-12/100(200) |
12 |
||||||
(H)RW12-15/100(200) |
15 |
||||||
(H)PRWG1-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)PRWG1-12F/100(200) |
12 |
||||||
(H)RW33-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW33-15/100(200) |
15 |
||||||
(H)RW5-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)RW10-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)PRWG2-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |