Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 outdoor high voltage vacuum circuit breaker, endearingly termed the 'circuit breaker.' This exemplary piece of outdoor distribution switchgear is meticulously engineered to function at a rated voltage of 12kV, powered by a robust three-phase AC of 50Hz. This versatile circuit breaker adeptly manages the interruption and reconnection of load current, overload current, and short circuit current, maintaining the integrity of the power grid. It is equipped with advanced overload and short circuit protective capabilities, meticulously addressing control and measurement requirements while offering sophisticated remote control and monitoring functionalities. Its widespread application spans across substations, industrial environments, and mining enterprise distribution systems, providing unmatched control and operational excellence, making it an ideal choice for environments that demand frequent operations.
Structural features:
Meticulously crafted, the circuit breaker features an innovative three-phase pillar dry design;
Designed with a fully enclosed structure, it provides exceptional sealing, outstanding moisture resistance, and anti-condensation properties, making it the perfect choice for high-temperature, humid regions;
Utilizes cutting-edge vacuum arc extinguishing technology to ensure extraordinary insulation reliability;
Offers impeccable opening and closing performance, guaranteeing safety without the risk of combustion or explosion;
Compact and lightweight, it requires no maintenance and promises an impressive lifespan;
Provides versatile operation with manual, electric, or remote control options;
The operating mechanism is expertly sealed at the base of the switch box, providing effective protection against outdoor environmental corrosion;
Boasts a novel, simplistic design with a dynamic mechanism that ensures reliable performance, a compact form, and an impressive service life of up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |