Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker: the unparalleled solution tailored for today's sophisticated outdoor distribution networks. Affectionately termed as the 'circuit breaker,' this advanced switchgear is expertly crafted with a 12kV rated voltage, operating seamlessly within a robust three-phase AC at 50Hz. This high-performance circuit breaker is engineered to effortlessly handle the interruption and reconnection of load current, overload current, and short circuit current within power grids. Boasting state-of-the-art overload and short circuit protection capabilities, it seamlessly fulfills control and measurement requirements while providing advanced remote control and monitoring functionalities. Widely applicable across substations, industrial settings, and mining enterprises, it stands as the ultimate choice for environments demanding frequent operation cycles. This ensures unparalleled control and efficiency, rendering it an indispensable asset for modern electrical infrastructures.
Structural Features:
Meticulously crafted with precision engineering, the circuit breaker showcases a refined three-phase pillar dry design, ensuring exceptional reliability and performance;
Expertly engineered with a fully enclosed structure, it delivers outstanding sealing, remarkable moisture resistance, and possesses anti-condensation attributes, making it ideal for high-temperature and humid environments;
Utilizes cutting-edge vacuum arc extinguishing technology, ensuring exceptional insulation reliability and performance;
Guarantees impeccable opening and closing performance, ensuring safety with no risk of combustion or explosion, providing peace of mind;
Designed to be compact and lightweight, this sophisticated device is maintenance-free, boasting an impressive lifespan that ensures enduring reliability;
Features versatile operation capabilities with options for manual, electric, or remote control, offering utmost convenience tailored to diverse needs;
The operating mechanism is securely sealed at the switch box's base, effectively safeguarding against outdoor environmental corrosion and damage;
Showcases an innovative and simplified design with a restless mechanism, ensuring reliable dynamic performance, a space-efficient structure, and an amazing service life reaching up to 10,000 cycles, setting a new standard in durability and reliability.
Main Technical Parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |