Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Step into the future of power management with the ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker – a trailblazer in modern outdoor distribution network solutions. Affectionately dubbed the 'circuit breaker,' this state-of-the-art switchgear is meticulously optimized for a 12kV rated voltage alongside a robust three-phase AC at 50Hz. Masterfully designed to handle the complexities of load current interruptions and reconnections, it excels in managing overload and short circuit currents with precision. Boasting revolutionary overload and short circuit protection, it flawlessly aligns with control and measurement demands while offering cutting-edge remote control and monitoring capabilities. Its vast application spectrum encompasses substations, industrial landscapes, and mining enterprise distribution systems, establishing it as the quintessential choice for environments necessitating frequent operations, ensuring unparalleled control, efficiency, and reliability.
Structural Features:
Meticulously crafted with a refined three-phase pillar dry design, this circuit breaker stands as a testament to engineering excellence;
Expertly designed with a fully enclosed structure, it delivers exceptional sealing properties, remarkable moisture resistance, and anti-condensation capabilities, making it perfect for high-temperature and humid conditions;
Incorporates cutting-edge vacuum arc extinguishing technology, providing unrivaled insulation reliability;
Guarantees impeccable safety in its opening and closing performance, eliminating any risk of combustion or explosion;
Boasts a compact and lightweight design, offering maintenance-free operation and a remarkable lifespan;
Offers versatile operation modes with options for manual, electric, or remote control, enhancing adaptability;
The operating mechanism is securely sealed at the base of the switch box, providing superior protection against harsh outdoor environmental corrosion;
Presents an innovative and simplified design featuring a restless mechanism, ensuring reliable dynamic performance, a compact structure, and an impressive service life reaching an astonishing 10,000 cycles.
Main Technical Parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |