Customization: | Available |
---|---|
Breaking Capacity: | 12kv/24kv/40.5kv |
Type: | Current Fuse |
Still deciding? Get samples of US$ 30/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
(H) RW(F) series outdoor high voltage AC drop fuse, affectionately known as the 'fuse', is ingeniously crafted for outdoor overhead distribution systems. It boasts a rated frequency of 50Hz and an impressive rated voltage of 10kV (options include 12/15/35/40.5). This remarkable device acts as a guardian angel for your circuit or electrical equipment, stepping in during overloads or short circuits within the power system. Under normal conditions, the fuse is seamlessly integrated into the power line, held in a tensioned elegance with a secured movable joint. In the event of line failures, the fault current triggers the fuse to blow, releasing the movable joint, promptly dropping the fuse tube to interrupt the circuit. This critical action not only safeguards maintenance personnel but also ensures the longevity and safety of your line and equipment. Enhanced with elastic contact and an arc extinguishing cover, the load type fuse is expertly designed to manage load currents within the power system efficiently.
The fuse adheres to stringent technical standards, including GB / T 15166.3 - 2008, which covers high voltage AC fuses - Part 3: injection fuses, and DL / T 640 - 1997, which pertains to outdoor AC high voltage drop-tested fuses and fuse links ordering technical conditions.
Working Environment:
Ambient temperature is versatile, ranging from a chilly -40°C to a warm +40°C;
Relative humidity is conscientiously regulated, with a daily average not exceeding 95%, and a monthly average under 90%;
The fuse is engineered to perform optimally at altitudes not surpassing 3000 meters;
The outdoor wind speed is masterfully handled, not exceeding 34 meters per second;
Installation site requirements: free from fire, explosion hazards, and corrosive chemical gases, ensuring a well-ventilated environment for paramount safety.
Note: Should the normal usage conditions be exceeded, bespoke solutions can be negotiated directly with our esteemed company.
Technical Parameters
Note: We proudly offer customization, tailoring products meticulously to meet your exact specifications.
Model |
Voltage |
Current |
Rated maximum
breaking current |
1min power frequency dry withstand
voltage |
1min power frequency wet withstand
voltage |
Rated lightning impulse withstand
voltage |
Opening and closing
load current |
XS-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
XS-15/100(200) |
15 |
||||||
PD-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
PD-15/100(200) |
15 |
||||||
(H)RW3-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW3-12/100(200) |
12 |
||||||
(H)RW4-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW4-12/100(200) |
12 |
||||||
(H)RW7-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW7-12/100(200) |
12 |
||||||
(H)RW10-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW10-12/100(200) |
12 |
||||||
(H)RW10-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW10-12F/100(200) |
12 |
||||||
(H)RW11-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
! |
(H)RW11-12/100(200) |
12 |
||||||
(H)RW11-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW11-12F/100(200) |
12 |
||||||
(H)RW12-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
45 |
30 |
105 |
/ |
(H)RW12-12/100(200) |
12 |
||||||
(H)RW12-15/100(200) |
15 |
||||||
(H)PRWG1-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)PRWG1-12F/100(200) |
12 |
||||||
(H)RW33-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW33-15/100(200) |
15 |
||||||
(H)RW5-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)RW10-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)PRWG2-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |