Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 outdoor high voltage vacuum circuit breaker, fondly referred to as the 'circuit breaker.' This outstanding piece of outdoor distribution switchgear operates efficiently at a noble rated voltage of 12kV, featuring a dynamic three-phase AC of 50Hz. It adeptly manages the interruption and connection of load current, overload current, and short circuit current within the power grid. This remarkable circuit breaker exhibits cutting-edge overload and short circuit protective capabilities, effortlessly meeting control and measurement criteria while providing state-of-the-art remote control and monitoring functions. Its extensive application ranges from substations to industrial locations and mining enterprise distribution systems, offering unrivaled control and operation, particularly suited to environments characterized by frequent operations.
Structural features:
Expertly crafted, the circuit breaker boasts a three-phase pillar dry design;
Designed with a fully enclosed structure, it offers unmatched sealing, outstanding moisture resistance, and anti-condensation qualities, making it an ideal choice for high-temperature and humid environments;
Incorporates cutting-edge vacuum arc extinguishing technology to ensure exceptional insulation reliability;
Provides impeccable opening and closing performance, guaranteeing safety with no risk of combustion or explosion;
Being compact and lightweight, it requires no maintenance and guarantees an impressive lifespan;
Offers operational versatility with manual, electric, or remote control options available;
The operating mechanism is carefully sealed at the base of the switch box, effectively protecting against outdoor environmental corrosion;
Features a novel and simplistic design with a restless mechanism, ensuring reliable dynamic performance, a compact form, and an extraordinary service life of up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |