The ZW32-12 outdoor high voltage vacuum circuit breaker, fondly called the 'circuit breaker,' is an outstanding piece of outdoor distribution switchgear meticulously crafted for a rated voltage of 12kV along with a resilient three-phase AC of 50Hz. This adaptable circuit breaker expertly manages the disruption and reconnection of load current, overload current, and short circuit current within the power grid. It integrates advanced protective features against overloads and short circuits, effortlessly meeting control and measurement standards while offering sophisticated remote control and monitoring capabilities. Its extensive application encompasses substations, industrial settings, and mining enterprise distribution systems, delivering extraordinary control and operation—tailored for environments demanding frequent operations.
Structural features:
Engineered with precision, the circuit breaker presents a three-phase pillar dry design;
Designed with a fully enclosed structure, it provides exceptional sealing, unparalleled moisture resistance, and anti-condensation benefits, rendering it the ideal solution for high-temperature and humid environments;
Utilizes cutting-edge vacuum arc extinguishing technology to ensure superior insulation reliability;
Achieves perfect opening and closing performance, ensuring safety with zero risk of combustion or explosion;
Compact, lightweight, maintenance-free, and promises a remarkable lifespan;
Versatile in its operations—offering manual, electric, or remote control options;
The operating mechanism is carefully sealed at the base of the switch box, effectively protecting against external environmental corrosion;
Features an innovative, simplistic design with a reliable mechanism ensuring consistent dynamic performance, compact structure, and an astonishing service life reaching up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |