Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 outdoor high voltage vacuum circuit breaker, a marvel of engineering and affectionately referred to as the 'circuit breaker.' This exemplary outdoor distribution switchgear is masterfully crafted to operate at a rated voltage of 12kV, powered by a solid three-phase AC of 50Hz. This versatile circuit breaker excels in managing the interruption and connection of load current, overload current, and short circuit current within the intricate power grid. It is equipped with cutting-edge overload and short circuit protection capabilities, seamlessly meeting control and measurement standards while offering advanced remote control and monitoring features. It finds extensive application in substations, industrial arenas, and mining enterprise distribution systems, delivering unparalleled control and operational excellence, particularly in environments where frequent operations are the norm.
Structural Features:
Crafted with utmost precision, the circuit breaker presents a three-phase pillar dry design, showcasing exceptional engineering prowess.
Designed with a fully enclosed structure, it provides superior sealing along with unmatched moisture resistance and anti-condensation characteristics, making it the optimal choice for high-temperature and humid regions.
Incorporates state-of-the-art vacuum arc extinguishing technology, ensuring outstanding insulation reliability and performance.
Delivers impeccable opening and closing performance, ensuring maximum safety with no risk of combustion or explosion, thus enhancing peace of mind.
Compact and lightweight, this maintenance-free marvel promises an impressive lifespan, making it a cost-effective choice for the long term.
Offers remarkable versatility in operation with options for manual, electric, or remote control, catering to diverse operational needs.
The operating mechanism is expertly sealed at the base of the switch box, providing effective protection against outdoor environmental corrosion, thereby ensuring longevity.
Featuring a novel and simplistic design, it includes a restless mechanism that guarantees reliable dynamic performance, compact form, and an astounding service life of up to 10,000 cycles, setting a new standard in durability.
Main Technical Parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |