Customization: | Available |
---|---|
Breaking Capacity: | 12kv/24kv/40.5kv |
Type: | Current Fuse |
Still deciding? Get samples of US$ 30/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
(H) RW(F) Series Outdoor High Voltage AC Drop Fuse, an innovative solution by Beierbian Group Co., Ltd, stands at the forefront of safety and efficiency. Designed meticulously for outdoor overhead distribution systems, it operates at a standard frequency of 50Hz and is compatible with voltages of 10kV (12/15/35/40.5). This fuse acts as a guardian for your circuits and electrical equipment, providing crucial protection against overloads and short circuit faults in power systems. Its integration in the power line ensures seamless operation; the fuse remains tensioned and securely locked during normal conditions. In the event of a fault, the resulting fault current triggers the fuse, releasing the movable joint, swiftly dropping the fuse tube, and disconnecting the circuit to ensure optimal safety. Enhanced with elastic contact and an arc extinguishing cover, this load type fuse not only opens and closes the load current efficiently but also ensures unparalleled safety in power system operations.
Our fuses are manufactured to exceed industry standards, complying with rigorous specifications like GB / T 15166.3 - 2008, which pertains to high voltage AC fuses, Part 3: injection fuses, as well as DL / T 640 - 1997, which covers the technical conditions for outdoor AC high voltage drop tested fuses and fuse links. These standards guarantee the reliability and superior performance of our product.
Working Environment:
Ambient temperature: Within the range of -40°C to +40°C;
Relative humidity: Designed to withstand a daily average humidity of up to 95%, and a monthly average not exceeding 90%;
Installation altitudes: Suitable for locations not surpassing 3000 meters;
Outdoor resilience: Capable of enduring wind speeds up to 34 meters/second;
Ideal installation sites: Must be free from fire, explosion hazards, chemical corrosive gases, and should be well-ventilated to ensure safety and longevity.
Note: For applications exceeding these standard conditions, our team at Beierbian Group Co., Ltd is prepared to discuss tailored solutions to meet your specific requirements.
Technical Parameters
Note: We at Beierbian Group Co., Ltd are committed to fulfilling your specific needs and can supply customized products according to your precise requirements.
Model |
Voltage |
Current |
Rated maximum
breaking current |
1min power frequency dry withstand
voltage |
1min power frequency wet withstand
voltage |
Rated lightning impulse withstand
voltage |
Opening and closing
load current |
XS-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
XS-15/100(200) |
15 |
||||||
PD-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
PD-15/100(200) |
15 |
||||||
(H)RW3-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW3-12/100(200) |
12 |
||||||
(H)RW4-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW4-12/100(200) |
12 |
||||||
(H)RW7-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW7-12/100(200) |
12 |
||||||
(H)RW10-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW10-12/100(200) |
12 |
||||||
(H)RW10-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW10-12F/100(200) |
12 |
||||||
(H)RW11-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
! |
(H)RW11-12/100(200) |
12 |
||||||
(H)RW11-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW11-12F/100(200) |
12 |
||||||
(H)RW12-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
45 |
30 |
105 |
/ |
(H)RW12-12/100(200) |
12 |
||||||
(H)RW12-15/100(200) |
15 |
||||||
(H)PRWG1-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)PRWG1-12F/100(200) |
12 |
||||||
(H)RW33-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW33-15/100(200) |
15 |
||||||
(H)RW5-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)RW10-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)PRWG2-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |