Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker, your ultimate solution for the demands of contemporary outdoor distribution networks. Esteemed by experts as the 'circuit breaker,' it is ingeniously crafted for a sophisticated 12kV rated voltage with a robust three-phase AC at 50Hz. This brilliant piece of advanced switchgear showcases its prowess in managing the seamless interruption and reconnection of load current, overload current, and short circuit current within power grids. With its cutting-edge overload and short circuit protective capabilities, it astutely caters to control and measurement needs while offering refined remote control and monitoring functionalities. Its vast application potential effortlessly covers substations, industrial hubs, and mining enterprise distribution systems, solidifying its status as the premier choice for environments where frequent operations are paramount. This ensures unparalleled control and efficiency, making it an indispensable asset for today's modern electrical infrastructures.
Structural Features:
Meticulously crafted with precision, this circuit breaker boasts a refined three-phase pillar dry design, exemplifying engineering excellence;
Expertly engineered with a fully enclosed structure, it provides outstanding sealing and boasts exceptional moisture resistance and anti-condensation characteristics, perfect for high-temperature and humid environments;
Employing state-of-the-art vacuum arc extinguishing technology, it offers extraordinary insulation reliability, setting new standards;
Ensures flawless opening and closing performance, guaranteeing safety with no risk of combustion or explosion, epitomizing safety excellence;
Designed to be compact and lightweight, this sophisticated device is maintenance-free and promises an impressive lifespan, exceeding industry expectations;
Features versatile operation capabilities, including manual, electric, or remote control options, ensuring utmost convenience and adaptability;
The operating mechanism is expertly sealed at the switch box's base, effectively safeguarding against the elements and ensuring protection from outdoor environmental corrosion;
Showcases an innovative and simplified design that includes a restless mechanism, ensuring reliable dynamic performance, a compact structure, and an astonishing service life reaching up to 10,000 cycles, guaranteeing longevity and reliability.
Main Technical Parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |