Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Meet the ZW32-12, a high-performance outdoor high voltage vacuum circuit breaker from Beierbian Group Co., Ltd. Known affectionately as the 'circuit breaker,' this piece of cutting-edge technology excels as an outdoor distribution switchgear. It operates seamlessly at a rated voltage of 12kV with a durable three-phase AC of 50Hz. Engineered for excellence, this versatile circuit breaker adeptly manages the interruption and connection of load current, overload current, and short circuit current within power grids. With its advanced protective capabilities against overloads and short circuits, it not only fulfills control and measurement specifications but also offers sophisticated remote control and monitoring functionalities. Its impressive versatility makes it indispensable in substations, industrial environments, and mining enterprise distribution systems, delivering unparalleled control and operation. This circuit breaker is ideal for settings with frequent operations, embodying both reliability and efficiency.
Structural features:
Crafted with meticulous precision, the circuit breaker features a three-phase pillar dry design, ensuring reliability and robustness in every use;
Designed with a fully enclosed structure, it provides outstanding sealing while offering exceptional moisture resistance and anti-condensation properties. This makes it an optimal choice for high-temperature and humid regions, where lesser designs would falter;
Utilizes cutting-edge vacuum arc extinguishing technology, providing remarkable insulation reliability that ensures safety and performance;
Boasts flawless opening and closing performance, guaranteeing safety without the risk of combustion or explosion, thereby offering peace of mind in any application;
This compact and lightweight equipment requires no maintenance and promises an impressive lifespan, making it a cost-effective and reliable choice;
Offers versatile operation modes, with manual, electric, or remote control options available, catering to diverse operational needs;
The operating mechanism is expertly sealed at the base of the switch box, providing effective protection from outdoor environmental corrosion, thus enhancing durability;
Features a novel, simplistic design with a restless mechanism that ensures reliable dynamic performance. Its compact form factor and an astounding service life of up to 10,000 cycles make it a leader in its class.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |