Our S-M series three-phase oil-immersed transformers feature a fully oil-filled, sealed corrugated oil tank that flexes with the oil's expansion, ensuring optimal heat dissipation and maintaining high efficiency with minimal losses.
This design significantly reduces power consumption and operational costs, making it ideal for power plants, substations, industrial and mining enterprises, as well as ports and airports, ensuring sustainable performance in environmentally sensitive areas.
Standard: Complies with IEC60076-1, IEC60076-2, IEC60076-3, IEC60076-5, and IEC60076-10, affirming our commitment to international excellence.
1. Operates efficiently between an ambient temperature range of +40°C and -25ºC, adapting to diverse climatic conditions.
2. Built to withstand an average temperature of +30ºC during the hottest month and +20ºC throughout the hottest year.
3. Designed for altitudes up to 1000 meters, ensuring reliability at various elevations.
4. Requires a power supply voltage waveform akin to a sine wave for optimal performance.
5. Ensures stability with a three-phase supply voltage that remains approximately symmetrical.
6. Maintains a total harmonic content of the load current under 5% of the rated current, preserving performance integrity.
7. Versatile in application, suitable for both indoor and outdoor environments.
1. Boasts high efficiency, low loss, and an impressively low noise profile, setting a new standard for transformer performance.
2. Features high mechanical strength with a balanced ampere-turn distribution and formidable short-circuit resistance, ensuring long-term durability.
3. Offers minimal no-load and load loss, enhancing energy savings and operational efficiency.
4. Designed for compactness and reliability, this transformer promises a long service life and is virtually maintenance-free.
Structure
Iron core:
Iron core:
Crafted from high-quality, high-performance, high-permeability silicon steel sheets, the iron core ensures low no-load loss, optimizing energy efficiency.
High/low voltage winding:
Ingeniously designed, the low-voltage winding up to 500KVA utilizes a layer type, while the new spiral type is employed for 630KVA and above, ensuring a perfect balance of performance and strength.
Engineered to exhibit high mechanical strength with a balanced ampere-turn distribution, these windings provide robust short-circuit resistance.
Fully sealed structure:
Our fully sealed construction employs a vacuum oil filling process, eliminating moisture and safeguarding the transformer oil from external air to prevent oil aging, thereby enhancing operational reliability.
Positioning structure:
Innovatively designed, the product features a positioning structure to prevent displacement during transport, with all fasteners meticulously engineered for security.
The product is meticulously designed with fastening nuts, ensuring that the fasteners remain secure and steadfast, even during extensive and prolonged operations. This guarantees the reliability and durability of the product over time.
Oil tank:
Our transformer features a state-of-the-art corrugated oil tank. This innovative design offers a straightforward process combined with exceptional mechanical strength. The superior welding effect ensures it is resistant to leaks, while the remarkable fluidity of the oil significantly enhances the heat dissipation capacity of the product, ensuring optimal performance.
Other configuration:
This transformer is equipped with a pressure relief valve and a signal thermometer, essential features that assure the safe and efficient operation of the transformer at all times.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Yzn11 |
130 | 630/600 | 2.3 | 4 | 745 | 530 | 890 | 280 |
50 | 170 | 910/870 | 2 | 790 | 560 | 940 | 365 | |||||
63 | 200 | 1090/1040 | 1.9 | 820 | 570 | 950 | 425 | |||||
80 | 250 | 1310/1250 | 1.9 | 850 | 580 | 1000 | 485 | |||||
100 | 290 | 1580/1500 | 1.8 | 900 | 620 | 1010 | 540 | |||||
125 | 340 | 1890/1800 | 1.7 | 880 | 630 | 1050 | 610 | |||||
160 | 400 | 2310/2200 | 1.6 | 950 | 690 | 1120 | 710 | |||||
200 | 480 | 2730/2600 | 1.5 | 990 | 730 | 1200 | 835 | |||||
250 | 560 | 3200/3050 | 1.4 | 1180 | 700 | 1200 | 970 | |||||
315 | 670 | 3830/3650 | 1.4 | 1230 | 760 | 1250 | 1125 | |||||
400 | 800 | 4520/4300 | 1.3 | 1260 | 800 | 1300 | 1310 | |||||
500 | 960 | 5410/5150 | 1.2 | 1400 | 900 | 1320 | 1530 | |||||
630 | Dyn11 Yyn0 Yzn11 |
1200 | 6200 | 1.1 | 4.5 | 1530 | 940 | 1350 | 1890 | |||
800 | 1400 | 7500 | 1 | 1580 | 1000 | 1420 | 2185 | |||||
1000 | 1700 | 10300 | 1 | 1770 | 1180 | 1450 | 2480 | |||||
1250 | 1950 | 12000 | 0.9 | 1920 | 1290 | 1430 | 3020 | |||||
1600 | 2400 | 14500 | 0.8 | 1990 | 1340 | 1620 | 3550 | |||||
2000 | 3000 | 17100 | 0.7 | 5 | 1950 | 1680 | 2100 | 4530 | ||||
2500 | 3300 | 23200 | 0.7 | 2020 | 1710 | 2100 | 5030 |
Note 1: For transformers with a rated capacity of 500kVA and below, refer to the load loss values above the diagonal line in the table for Dyn11 or Yzn11 coupling groups. For the Yyn0 coupling group, refer to the values below the diagonal line.
Note 2: Achieve peak operational efficiency when the transformer's average annual load rate is between 35% and 40% by utilizing the specified loss values in the table.
Overall and mounting dimensions(mm)
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Yzn11 |
100 | 630/600 | 1.5 | 4 | 690 | 510 | 920 | 275 |
50 | 130 | 910/870 | 1.3 | 730 | 510 | 960 | 340 | |||||
63 | 150 | 1090/1040 | 1.2 | 750 | 550 | 1000 | 385 | |||||
80 | 180 | 1310/1250 | 1.2 | 790 | 620 | 1020 | 450 | |||||
100 | 200 | 1580/1500 | 1.1 | 790 | 700 | 1040 | 520 | |||||
125 | 240 | 1890/1800 | 1.1 | 840 | 800 | 1070 | 625 | |||||
160 | 280 | 2310/2200 | 1 | 1070 | 670 | 1130 | 695 | |||||
200 | 340 | 2730/2600 | 1 | 1140 | 750 | 1140 | 795 | |||||
250 | 400 | 3200/3050 | 0.9 | 1200 | 800 | 1190 | 955 | |||||
315 | 480 | 3830/3650 | 0.9 | 1300 | 860 | 1210 | 1085 | |||||
400 | 570 | 4520/4300 | 0.8 | 1380 | 900 | 1240 | 1290 | |||||
500 | 680 | 5410/5100 | 0.8 | 1450 | 950 | 1300 | 1590 | |||||
630 | Dyn11 Yyn0 Yzn11 |
810 | 6200 | 0.6 | 4.5 | 1500 | 970 | 1360 | 1850 | |||
800 | 980 | 7500 | 0.6 | 1660 | 1140 | 1400 | 2210 | |||||
1000 | 1150 | 10300 | 0.6 | 1690 | 1190 | 1530 | 2570 | |||||
1250 | 1360 | 12000 | 0.5 | 1760 | 1230 | 1600 | 3115 | |||||
1600 | 1640 | 14500 | 0.5 | 1800 | 1250 | 1660 | 3520 | |||||
2000 | 1940 | 18300 | 0.4 | 5 | 1930 | 1360 | 1490 | 4060 | ||||
2500 | 2290 | 21200 | 0.4 | 2080 | 1360 | 1570 | 5105 |
Note 1: For transformers with a rated capacity of 500kVA and below, use the load loss values above the diagonal for Dyn11 or Yzn11 coupling groups. Values below the diagonal apply to the Yyn0 coupling group.
Note 2: To achieve maximum operating efficiency when the average annual load rate of the transformer is between 35% and 40%, leverage the loss values indicated in the table.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Yzn11 |
80 | 630/600 | 1.5 | 4 | 685 | 490 | 860 | 260 |
50 | 100 | 910/870 | 1.3 | 725 | 520 | 955 | 365 | |||||
63 | 110 | 1090/1040 | 1.2 | 750 | 535 | 970 | 415 | |||||
80 | 130 | 1310/1250 | 1.2 | 770 | 565 | 985 | 465 | |||||
100 | 150 | 1580/1500 | 1.2 | 800 | 595 | 1000 | 545 | |||||
125 | 170 | 1890/1800 | 1.1 | 815 | 670 | 1010 | 585 | |||||
160 | 200 | 2310/2200 | 1.1 | 1015 | 645 | 1055 | 695 | |||||
200 | 240 | 2730/2600 | 1 | 1020 | 650 | 1115 | 810 | |||||
250 | 290 | 3200/3050 | 1 | 1140 | 730 | 1120 | 930 | |||||
315 | 340 | 3830/3650 | 0.9 | 1195 | 785 | 1175 | 1075 | |||||
400 | 410 | 4520/4300 | 0.9 | 1265 | 855 | 1195 | 1255 | |||||
500 | 480 | 5410/5100 | 0.8 | 1325 | 915 | 1240 | 1435 | |||||
630 | Dyn11 Yyn0 Yzn11 |
570 | 6200 | 0.8 | 4.5 | 1465 | 960 | 1295 | 1880 | |||
800 | 700 | 7500 | 0.6 | 1515 | 995 | 1340 | 2145 | |||||
1000 | 830 | 10300 | 0.6 | 1605 | 1095 | 1460 | 2455 | |||||
1250 | 970 | 12000 | 0.5 | 1685 | 1145 | 1485 | 2840 | |||||
1600 | 1170 | 14500 | 0.5 | 1775 | 1225 | 1580 | 3310 | |||||
2000 | 1550 | 18300 | 0.4 | 5 | 1855 | 1265 | 1600 | 3960 | ||||
2500 | 1830 | 21200 | 0.4 | 1885 | 1305 | 1780 | 4980 |
Note 1: For transformers rated at 500kVA and below, apply the load loss values above the diagonal for Dyn11 or Yzn11 coupling groups. Those below the diagonal are for the Yyn0 coupling group.
Note 2: When the transformer's average annual load rate is between 35% and 40%, the loss values in the table provide maximum operational efficiency.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Yzn11 |
80 | 505/480 | 1.5 | 4 | 785 | 710 | 880 | 370 |
50 | 100 | 730/695 | 1.3 | 800 | 730 | 940 | 480 | |||||
63 | 110 | 870/830 | 1.2 | 815 | 720 | 970 | 535 | |||||
80 | 130 | 1050/1000 | 1.2 | 830 | 740 | 990 | 580 | |||||
100 | 150 | 1260/1200 | 1.1 | 875 | 790 | 1010 | 705 | |||||
125 | 170 | 1510/1440 | 1.1 | 875 | 770 | 1050 | 775 | |||||
160 | 200 | 1850/1760 | 1 | 935 | 820 | 1140 | 975 | |||||
200 | 240 | 2180/2080 | 1 | 995 | 870 | 1140 | 1140 | |||||
250 | 290 | 2560/2440 | 0.9 | 995 | 900 | 1180 | 1240 | |||||
315 | 340 | 3060/2920 | 0.9 | 1030 | 880 | 1250 | 1425 | |||||
400 | 410 | 3610/3440 | 0.8 | 1075 | 910 | 1270 | 1635 | |||||
500 | 480 | 4330/4120 | 0.8 | 1120 | 930 | 1320 | 1950 | |||||
630 | Dyn11 Yyn0 Yzn11 |
570 | 4960 | 0.6 | 4.5 | 1165 | 950 | 1350 | 2150 | |||
800 | 700 | 6000 | 0.6 | 1210 | 1050 | 1390 | 2515 | |||||
1000 | 830 | 8240 | 0.6 | 1520 | 1020 | 1450 | 2635 | |||||
1250 | 970 | 9600 | 0.5 | 1630 | 1090 | 1540 | 3210 | |||||
1600 | 1170 | 11600 | 0.5 | 1680 | 1150 | 1600 | 3905 | |||||
2000 | 1550 | 14600 | 0.4 | 5 | 1890 | 1300 | 1600 | 4130 | ||||
2500 | 1830 | 16900 | 0.4 | 1990 | 1360 | 1700 | 5250 |
Note 1: For transformers with rated capacities up to 500kVA, use load loss values above the diagonal for Dyn11 or Yzn11 coupling groups, and those below for the Yyn0 coupling group.
Note 2: Attain optimal efficiency at an annual load rate of 35% to 40% by applying the prescribed loss values in the table.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Dyn5 |
70 | 505 | 1.2 | 4 | 785 | 710 | 880 | / |
50 | 90 | 730 | 1.04 | 800 | 730 | 940 | / | |||||
80 | 115 | 1050 | 0.96 | 830 | 740 | 990 | / | |||||
100 | 135 | 1265 | 0.88 | 875 | 790 | 1010 | / | |||||
125 | 150 | 1510 | 0.88 | 875 | 770 | 1050 | / | |||||
160 | 180 | 1850 | 0.8 | 935 | 820 | 1140 | / | |||||
200 | 215 | 2185 | 0.8 | 995 | 870 | 1140 | / | |||||
250 | 260 | 2560 | 0.72 | 995 | 900 | 1180 | / | |||||
315 | 305 | 3065 | 0.72 | 1030 | 880 | 1250 | / | |||||
400 | 370 | 3615 | 0.64 | 1075 | 910 | 1270 | / | |||||
500 | 430 | 4330 | 0.64 | 1120 | 930 | 1320 | / | |||||
630 | 510 | 4960 | 0.48 | 4.5 | 1165 | 950 | 1350 | / | ||||
800 | 630 | 6000 | 0.48 | 1210 | 1050 | 1390 | / | |||||
1000 | 745 | 8240 | 0.48 | 1520 | 1020 | 1450 | / | |||||
1250 | 870 | 9600 | 0.4 | 1630 | 1090 | 1540 | / | |||||
1600 | 1050 | 11600 | 0.4 | 1680 | 1150 | 1600 | / | |||||
2000 | 1225 | 14640 | 0.32 | 5 | 1890 | 1300 | 1600 | / | ||||
2500 | 1440 | 14840 | 0.32 | 1990 | 1360 | 1700 | / |
Note 1: For transformers rated up to 500kVA, load loss values above the diagonal are for Dyn11 or Yzn11 coupling groups, while those below are for the Yyn0 coupling group.
Note 2: The table provides optimal efficiency loss values when the average annual load rate is 35% to 40%.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Dyn5 |
65 | 455 | 1.2 | 4 | 785 | 710 | 880 | / |
50 | 80 | 655 | 1.04 | 800 | 730 | 940 | / | |||||
80 | 105 | 945 | 0.96 | 830 | 740 | 990 | / | |||||
100 | 120 | 1140 | 0.88 | 875 | 790 | 1010 | / | |||||
125 | 135 | 1360 | 0.88 | 875 | 770 | 1050 | / | |||||
160 | 160 | 1665 | 0.8 | 935 | 820 | 1140 | / | |||||
200 | 190 | 1970 | 0.8 | 995 | 870 | 1140 | / | |||||
250 | 230 | 2300 | 0.72 | 995 | 900 | 1180 | / | |||||
315 | 270 | 2760 | 0.72 | 1030 | 880 | 1250 | / | |||||
400 | 330 | 3250 | 0.64 | 1075 | 910 | 1270 | / | |||||
500 | 385 | 3900 | 0.64 | 1120 | 930 | 1320 | / | |||||
630 | 460 | 4460 | 0.48 | 4.5 | 1165 | 950 | 1350 | / | ||||
800 | 560 | 5400 | 0.48 | 1210 | 1050 | 1390 | / | |||||
1000 | 665 | 7415 | 0.48 | 1520 | 1020 | 1450 | / | |||||
1250 | 780 | 8640 | 0.4 | 1630 | 1090 | 1540 | / | |||||
1600 | 940 | 10440 | 0.4 | 1680 | 1150 | 1600 | / | |||||
2000 | 1085 | 13180 | 0.32 | 5 | 1890 | 1300 | 1600 | / | ||||
2500 | 1280 | 13360 | 0.32 | 1990 | 1360 | 1700 | / |
Note 1: For transformers with a rated capacity of 500kVA and below, the technical prowess shines as the load loss values above the diagonal line in the table cater specifically to the Dyn11 or Yzn11 coupling group. Conversely, for the below diagonal line values, the Yyn0 coupling group benefits from the distinctive load loss characteristics.
Note 2: Achieve peak performance! When the average annual load rate of the transformer hovers between 35% and 40%, by utilizing the meticulously calculated loss value in the table, you can unlock the maximum operational efficiency, ensuring optimal functionality.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
25 | 20 10 6 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Dyn5 |
63 | 600 | 1.7 | 5.5(20kV) 4 (6kV, 10kV) |
1090 | 600 | 1150 | / |
50 | 81 | 750 | 1.6 | 1120 | 620 | 1180 | / | |||||
100 | 130 | 1250 | 1.3 | 1150 | 650 | 1290 | / | |||||
160 | 189 | 1750 | 1.1 | 1160 | 675 | 1380 | / | |||||
250 | 270 | 2350 | 0.96 | 1200 | 880 | 1400 | / | |||||
315 | 324 | 2800 | 0.88 | 1230 | 920 | 1460 | / | |||||
400 | 387 | 3250 | 0.8 | 1250 | 950 | 1580 | / | |||||
500 | 459 | 3900 | 0.8 | 1390 | 960 | 1580 | / | |||||
630 | 540 | 4600 | 0.72 | 6(20kV) 4.5 (6kV, 10kV) |
1450 | 980 | 1600 | / | ||||
800 | 585 | 6000 | 0.64 | 1560 | 1020 | 1720 | / | |||||
1000 | 693 | 7600 | 0.56 | 1700 | 1070 | 1790 | / | |||||
1250 | 855 | 9500 | 0.56 | 1700 | 1070 | 1791 | / | |||||
1600 | 1080 | 12000 | 0.48 | 1850 | 1130 | 1850 | / | |||||
2000 | 1305 | 15000 | 0.48 | 6(20kV) 5 (6kV, 10kV) |
2000 | 1280 | 1980 | / | ||||
2500 | 1575 | 18500 | 0.4 | 2040 | 1320 | 2050 | / | |||||
3150 | 1980 | 23000 | 0.4 | 2200 | 1400 | 2250 | / |
Note 1: For transformers with a rated capacity of 500kVA and below, the technical prowess shines as the load loss values above the diagonal line in the table cater specifically to the Dyn11 or Yzn11 coupling group. Conversely, for the below diagonal line values, the Yyn0 coupling group benefits from the distinctive load loss characteristics.
Note 2: Achieve peak performance! When the average annual load rate of the transformer hovers between 35% and 40%, by utilizing the meticulously calculated loss value in the table, you can unlock the maximum operational efficiency, ensuring optimal functionality.