Customization: | Available |
---|---|
Breaking Capacity: | 12kv/24kv/40.5kv |
Type: | Current Fuse |
Still deciding? Get samples of $ !
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
(H) RW(F) series outdoor high voltage AC drop fuse is a pinnacle of modern engineering, meticulously crafted for contemporary electrical systems. It stands as an exemplary solution for outdoor overhead distribution networks operating at a frequency of 50Hz, with a remarkable voltage range of 10kV (12/15/35/40.5). This fuse is indispensable for protecting circuits and electrical equipment from potential overloads or short-circuits within power systems. In regular conditions, it remains taut and secure within the power line, ensuring unbroken connections. However, in the event of a fault, the fuse's responsive design allows the fault current to trigger the fuse, causing the release of the movable joint. This swift reaction ensures the fuse tube drops promptly, cutting off the circuit and delivering critical safety protection during maintenance operations. With an elastic contact and a sophisticated arc extinguishing cover, this load type fuse is superbly efficient in opening and closing load currents within power systems.
Our fuse is expertly crafted to comply with stringent technical standards, such as GB / T 15166.3 - 2008 for high voltage AC fuses, Part 3: injection fuses, and DL / T 640 - 1997 for outdoor AC high voltage drop-tested fuses. These standards ensure unparalleled performance and reliability under specified technical conditions.
Working Environment:
Designed to operate within a wide ambient temperature range spanning from a frigid -40°C to a balmy +40°C, this product delivers robust performance across varied climates.
Boasting a relative humidity tolerance where the daily average remains below 95% and the monthly average does not exceed 90%, this fuse is adept at enduring high humidity conditions.
Suitable for altitudes not exceeding 3000 meters, it accommodates diverse geographical locations with ease.
Masterfully engineered to withstand outdoor wind speeds up to 34 meters per second, this fuse retains its stability and functionality even in windy conditions.
Installation sites must be free from fire, explosion hazards, and chemically corrosive gases, while ensuring proper ventilation to maintain optimal performance and safety.
Note: If standard usage conditions are exceeded, we encourage users to consult with our company to explore potential solutions that ensure ongoing safety and efficiency.
Technical parameters
Note: We offer tailored solutions, providing products customized to meet specific user requirements.
Model |
Voltage |
Current |
Rated maximum
breaking current |
1min power frequency dry withstand
voltage |
1min power frequency wet withstand
voltage |
Rated lightning impulse withstand
voltage |
Opening and closing
load current |
XS-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
XS-15/100(200) |
15 |
||||||
PD-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
PD-15/100(200) |
15 |
||||||
(H)RW3-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW3-12/100(200) |
12 |
||||||
(H)RW4-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW4-12/100(200) |
12 |
||||||
(H)RW7-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW7-12/100(200) |
12 |
||||||
(H)RW10-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW10-12/100(200) |
12 |
||||||
(H)RW10-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW10-12F/100(200) |
12 |
||||||
(H)RW11-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
! |
(H)RW11-12/100(200) |
12 |
||||||
(H)RW11-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW11-12F/100(200) |
12 |
||||||
(H)RW12-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
45 |
30 |
105 |
/ |
(H)RW12-12/100(200) |
12 |
||||||
(H)RW12-15/100(200) |
15 |
||||||
(H)PRWG1-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)PRWG1-12F/100(200) |
12 |
||||||
(H)RW33-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW33-15/100(200) |
15 |
||||||
(H)RW5-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)RW10-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)PRWG2-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |