Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The ZW32-12 outdoor high voltage vacuum circuit breaker, lovingly referred to as the 'circuit breaker,' stands as a sterling example of outdoor distribution switchgear. It operates proficiently at a rated voltage of 12kV, powered by a robust three-phase AC of 50Hz. This adaptive circuit breaker proficiently manages the interruption and connection of load current, overload current, and short circuit current within the power grid. It features cutting-edge overload and short circuit protective capabilities, effortlessly meeting control and measurement specifications while providing sophisticated remote control and monitoring functionalities. Its extensive application covers substations, industrial environments, and mining enterprises, where it delivers unmatched control and operation, making it ideal for frequently operational settings.
Structural features:
Meticulously crafted, the circuit breaker features a three-phase pillar dry design that embodies precision;
Designed with a fully enclosed structure, it offers outstanding sealing, exceptional moisture resistance, and anti-condensation properties, making it an unparalleled choice for high-temperature and humid regions;
Utilizes cutting-edge vacuum arc extinguishing technology for remarkable insulation reliability;
Ensures impeccable opening and closing performance, providing safety with no risk of combustion or explosion;
Compact and lightweight, this device requires no maintenance and promises an impressive operational lifespan;
Versatile in operation with options for manual, electric, or remote control;
The operating mechanism is expertly sealed at the base of the switch box, effectively protecting against outdoor environmental corrosion;
Exhibits a novel, simplistic design along with a resilient mechanism that guarantees reliable dynamic performance, a compact form, and an extraordinary service life of up to 10,000 cycles.
Main technical parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |