Customization: | Available |
---|---|
Type: | Power Source Arrester |
Structure: | Zinc Oxide Arrester |
Still deciding? Get samples of US$ 35/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The Zinc Oxide Arrester from Beierbian Group Co., Ltd is a cutting-edge, fully sealed, and exceptionally dependable lightning protection solution designed for the 10kV power distribution system. Expertly crafted from a zinc oxide valve column, complemented by upper and lower electrodes, and encased in integrally molded silicone rubber, this innovative device offers remarkable features:
Utilizing specially engineered valve plates and meticulously designed core parameters, this arrester is assured to withstand arc grounding, PT resonance, and various operational overvoltages with unwavering reliability. It is engineered to safely endure continuous operation under line voltage, as well as withstand power frequency overvoltages of 2.5 to 3 times. Its voltage endurance far surpasses international standards, boasting 1 to 3 orders of magnitude higher resilience.
Main Characteristics Of Jacket Materials And Product Usage Environment: Where Quality Meets Durability
Item |
Unit |
Norm |
Shore Hardness A |
/ |
60 |
Tensile Strength |
mpa |
≥35 |
Breaking Elongation |
% |
≥250 |
Oxygen Index |
/ |
45 |
Resistivity |
Ω.m |
≥1×1013 |
Breakdown Strength |
MV/m |
≥25 |
Tracking |
kV |
4.5 |
Durability |
Not less than 20 years |
Working Environment: Designed for Diverse Conditions
Perfect for both indoor and outdoor settings;
Operable at altitudes up to 3000m;
Thrives in ambient temperatures ranging from -40°C to +60°C;
Compatible with power supply frequencies between 48Hz and 62Hz;
Ensures the power frequency voltage applied between the arrester terminals remains within safe limits;
Resilient to seismic activities up to 8 degrees.
Capable of withstanding outdoor wind speeds up to 35 meters/second;
Important Note:
In cases where normal usage conditions are surpassed, users are encouraged to consult with us for tailored solutions.
Main Technical Parameters: The Blueprint of Excellence
Model |
Nominal Voltage (rms) |
Rated Voltage Of Arrester (rms) |
Continuous Operating Voltage (rms) |
DC 1mA reference voltage |
The residual voltage under nominal discharge current |
Steep wave impact residual voltage |
2ms square wave flow capacity |
Operation Place |
YH5WS-3.8/17 |
3 |
3.8 |
2.0 |
7.5 |
17.0 |
19.6 |
100 |
Distribution Type |
YH5WS-5/15 |
3 |
5 |
4.0 |
7.5 |
15.0 |
17.3 |
150 |
|
YH5WS-7.6/30 |
6 |
7.6 |
4.0 |
15.0 |
15.0 |
34.5 |
100 |
|
YH5WS-10/30 |
6 |
10 |
8.0 |
15.0 |
30.0 |
34.6 |
150 |
|
YH5WS-12.7/50 |
10 |
12.7 |
10 |
26.0 |
50.0 |
57.5 |
100 |
|
YH5WS-16.5/50 |
10 |
16.5 |
12.7 |
26.0 |
50.0 |
57.5 |
100 |
|
YH5WS-17/50 |
10 |
17 |
13.6 |
26.0 |
50.0 |
57.5 |
150 |
|
YH5WS-17/45 |
10 |
17 |
13.6 |
25.0 |
45.0 |
/ |
250 |
|
YH10WS-17/45 |
10 |
17 |
13.6 |
25.0 |
45.0 |
/ |
400 |
|
YH5WZ-5/13.5 |
3 |
5 |
4.0 |
7.2 |
13.5 |
15.5 |
200 |
Power Station Type |
YH5WZ-7.6/27 |
6 |
7.6 |
4.0 |
14.4 |
27.0 |
31.0 |
150 |
|
YH5WZ-10/27 |
6 |
10 |
8.0 |
14.4 |
27.0 |
31.0 |
200 |
|
YH5WZ-42/134 |
35 |
42 |
23.4 |
73 |
134 |
154 |
150 |
|
YH5WZ-12.7/45 |
10 |
12.7 |
6.6 |
24.0 |
45.0 |
51.8 |
150 |
|
YH5WZ-16.5/45 |
10 |
16.5 |
13.2 |
24.0 |
45.0 |
51.8 |
150 |
|
YH5WZ-17/45 |
10 |
17 |
13.6 |
24.0 |
45.0 |
51.8 |
200 |
|
YH5WZ-51/134 |
35 |
51 |
40.8 |
73.0 |
134 |
154 |
400 |
|
YH10WZ-17/45 |
10 |
17 |
13.6 |
24.0 |
45.0 |
51.8 |
200 |
|
YH10WZ-51/134 |
35 |
51 |
40.8 |
73.0 |
134 |
154 |
400 |
|
YH5WR-5/13.5 |
3 |
5 |
4.0 |
7.2 |
13.5 |
/ |
400 |
Capacitive Type |
YH5WR-7.6/27 |
6 |
7.6 |
4.0 |
13.8 |
27.0 |
/ |
400 |
|
YH5WR-10/27 |
6 |
10 |
8.0 |
14.4 |
27.0 |
/ |
400 |
|
YH5WR-12.7/45 |
10 |
12.7 |
6.6 |
23.0 |
45.0 |
/ |
400 |
|
YH5WR 17/45 |
10 |
17 |
13.6 |
24.0 |
45.0 |
/ |
400 |
|
YH5WX-51/134 |
35 |
51 |
40.8 |
73 |
134.0 |
154 |
400 |
Line type |
YH1.5W-30/80 |
35 |
30 |
24 |
44 |
80.0 |
/ |
600 |
Neutral Type |
Note: Polymeric Excellence in Design
Model |
Nominal Voltage (rms) |
Rated Voltage Of Arrester (rms) |
Continuous Operating Voltage (rms) |
DC 1mA Reference Voltage |
The Residual Voltage Under Nominal Discharge Current |
Steep Wave Impact Residual Voltage |
2ms Square Wave Flow Capacity |
Operation Place |
Y5WS-5/15 |
3 |
5 |
4.0 |
7.5 |
15.0 |
17.3 |
150 |
Distribution Type |
Y5WS-7.6/30 |
6 |
7.6 |
4.0 |
15.0 |
15.0 |
34.5 |
100 |
|
Y5WS-10/30 |
6 |
10 |
8.0 |
15.0 |
30.0 |
34.6 |
150 |
|
Y5WS-12.7/50 |
10 |
12.7 |
10 |
26.0 |
50.0 |
57.5 |
100 |
|
Y5WS-16.5/50 |
10 |
16.5 |
12.7 |
26.0 |
50.0 |
57.5 |
100 |
|
Y5WS-17/50 |
10 |
17 |
13.6 |
26.0 |
50.0 |
57.5 |
150 |
|
Y5WZ-5/13.5 |
3 |
5 |
4.0 |
7.2 |
13.5 |
15.5 |
200 |
Power Station Type |
Y5WZ-7.6/27 |
6 |
7.6 |
4.0 |
14.4 |
27.0 |
31.0 |
150 |
|
Y5WZ-10/27 |
6 |
10 |
8.0 |
14.4 |
27.0 |
31.0 |
200 |
|
Y5WZ-42/134 |
35 |
42 |
23.4 |
73 |
134 |
154 |
150 |
|
Y5WZ-12.7/45 |
10 |
12.7 |
6.6 |
24.0 |
45.0 |
51.8 |
150 |
|
Y5WZ-16.5/45 |
10 |
16.5 |
13.2 |
24.0 |
45.0 |
51.8 |
150 |
|
Y5WZ-17/45 |
10 |
17 |
13.6 |
24.0 |
45.0 |
51.8 |
200 |
|
Y5WZ-51/134 |
35 |
51 |
40.8 |
73.0 |
134 |
154 |
400 |
|
Y5WR-5/13.5 |
3 |
5 |
4.0 |
7.2 |
13.5 |
/ |
400 |
Capacitive Type |
Y5WR-7.6/27 |
6 |
7.6 |
4.0 |
13.8 |
27.0 |
/ |
400 |
|
Y5WR-10/27 |
6 |
10 |
8.0 |
14.4 |
27.0 |
/ |
400 |
|
Y5WR-12.7/45 |
10 |
12.7 |
6.6 |
23.0 |
45.0 |
/ |
400 |
|
Y5WR-17/45 |
10 |
17 |
13.6 |
24.0 |
45.0 |
/ |
400 |
|
Y1.5W-0.28/1.3 |
0.22 |
0.28 |
0.24 |
0.6 |
1.3 |
/ |
75 |
Low Voltage |
Y1.5W-0.5/2.6 |
0.38 |
0.5 |
0.24 |
1.2 |
2.6 |
/ |
75 |
|
Note:Porcelain |
Model |
Nominal Voltage |
Rated Voltage Of Arrester |
The Wave Front Steepness Of The Shock Discharge |
DC 1mA Reference Voltage kV Not Less Than |
1.2/50 Impulse Discharge Voltage Not Greater Than |
Wavefront Impulse Discharge Voltage
kV Not Greater Than |
The Residual Voltage Under Nominal Discharge Current 8/20μs
kV Not Greater Than |
2000μs Square Wave Flow Capacity |
4/10μs Impulse Current Capacity |
Y5CS-7.6/27 |
6 |
7.6 |
63 |
16 |
35 |
43.8 |
27 |
75 |
25 |
Y5CZ-7.6/24 |
6 |
7.6 |
63 |
16 |
30 |
37.5 |
24 |
150 |
40 |
Y5CS-12.7/45 |
10 |
12.7 |
106 |
26 |
50 |
62.5 |
45 |
75 |
25 |
Y5CS-12.7/41 |
10 |
12.7 |
106 |
26 |
45 |
56.5 |
41 |
200 |
40 |
Y5CZ-42/124 |
35 |
42.0 |
343 |
82 |
134 |
168 |
124 |
200 |
40 |
Note: Porcelain Series Gap Distinction
Installation: Steps for Seamless Setup
(1) Verify the nameplate before installation to ensure the arrester's system rated voltage aligns with the installation point's system voltage;
(2) Choose either suspension or vertical installation. If opting for vertical, ensure the arrester is not used as a load-bearing support insulator;
(3) Keep lead wires optimally short to maintain protection efficacy, and avoid excessive tension on the arrester.
Test: Guaranteeing Unmatched Reliability