Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker, a hallmark of innovation for today's outdoor distribution networks. This masterpiece, affectionately dubbed the 'circuit breaker,' is ingeniously crafted to operate at a 12kV rated voltage with a robust three-phase AC at 50Hz. This exceptional circuit breaker excels in the seamless disruption and reconnection of load current, overload current, and short circuit current within power grids. It sets the standard in overload and short circuit protection, adeptly fulfilling control and measurement requirements while offering advanced remote operation and monitoring capabilities. Its unparalleled versatility makes it perfect for substations, industrial sectors, and mining enterprise distribution systems, making it the ultimate choice for environments demanding frequent operations. This ensures supreme control and efficiency, rendering it an indispensable asset for cutting-edge electrical infrastructures.
Structural Features:
Meticulously crafted with precision, this circuit breaker boasts a sophisticated three-phase pillar dry design;
Expertly engineered with a fully enclosed structure, it delivers outstanding sealing, exceptional moisture resistance, and anti-condensation features, ideally suited for high-temperature and humid environments;
Employs cutting-edge vacuum arc extinguishing technology, providing exceptional insulation reliability;
Ensures flawless opening and closing performance, guaranteeing safety with zero risk of combustion or explosion;
Designed to be compact and lightweight, this elegant device requires no maintenance and boasts an impressive lifespan;
Features versatile operation capabilities, offering manual, electric, or remote control options for ultimate convenience;
The operating mechanism is skillfully sealed at the switch box's base, effectively protecting against outdoor environmental corrosion;
Showcases an innovative and simplified design with a dynamic restless mechanism, ensuring reliable dynamic performance, a compact structure, and a remarkable service life reaching up to 10,000 cycles.
Main Technical Parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |