Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Step into the future with the ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker from Beierbian Group Co., Ltd, a revolutionary masterpiece designed for cutting-edge outdoor distribution networks. Affectionately known as the 'circuit breaker,' this state-of-the-art technology is engineered for a robust 12kV rated voltage and a resilient three-phase AC at 50Hz, ensuring optimal performance. At the heart of this innovative circuit breaker is its superior ability to manage seamless interruptions and reconnections of load currents, overload currents, and even short circuit currents within power grids. Its advanced design ensures top-tier overload and short circuit protection, effortlessly catering to control and measurement requirements. With sophisticated remote control and monitoring functions, it is perfect for substations, industrial sectors, and mining distribution systems, making it an essential asset for environments demanding frequent operations. Elevate your modern electrical infrastructure with this unparalleled tool, promising unmatched control and efficiency.
Structural Features:
Crafted with remarkable precision, the circuit breaker presents a distinguished three-phase pillar dry design that epitomizes excellence;
Skillfully designed with a fully enclosed structure, it boasts extraordinary sealing, remarkable moisture resistance, and anti-condensation qualities. Perfectly suited for high-temperature and humid conditions;
Incorporates cutting-edge vacuum arc extinguishing technology, ensuring outstanding insulation reliability and safety;
Delivers flawless opening and closing performance, ensuring absolute safety without the risk of combustion or explosion;
Compact and lightweight, this advanced device is virtually maintenance-free, offering an impressive and prolonged operational lifespan;
Featuring versatile operation capabilities, it provides manual, electric, or remote control options, maximizing convenience and adaptability;
The operating mechanism is meticulously sealed at the switch box's base, offering robust protection against environmental corrosion outdoors;
Exhibits an innovative and streamlined design with a restless mechanism that guarantees reliable dynamic performance, a compact structure, and a phenomenal service life of up to 10,000 cycles.
Main Technical Parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |