Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of US$ 800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker - your pinnacle solution for modern outdoor distribution networks. Revered by industry experts as the 'circuit breaker,' this marvel of engineering is designed for a 12kV rated voltage and operates seamlessly on a robust three-phase AC at 50Hz. This powerhouse of a circuit breaker excels in the interruption and reconnection of load, overload, and short circuit currents, ensuring the utmost safety and reliability in power grids. With its superior overload and short circuit protective features, it transcends traditional switchgear by integrating sophisticated control, measurement, and remote monitoring capabilities. Its versatility shines in substations, industrial sectors, and mining enterprise distribution systems, establishing it as the premier choice for environments necessitating frequent operations. Harness this extraordinary device to achieve unparalleled control and efficiency, making it an indispensable cornerstone of contemporary electrical infrastructures.
Structural Features:
Meticulously crafted with a refined three-phase pillar dry design, this circuit breaker epitomizes precision and excellence;
Expertly engineered with a fully enclosed structure, it boasts outstanding sealing, exceptional moisture resistance, and anti-condensation attributes, perfect for high-temperature and humid environments;
Utilizes cutting-edge vacuum arc extinguishing technology, delivering exceptional insulation reliability to meet rigorous standards;
Ensures impeccable opening and closing performance, providing unparalleled safety with no risk of combustion or explosion;
Designed to be compact and lightweight, this sophisticated device is maintenance-free and boasts an impressive lifespan;
Features versatile operation capabilities, offering manual, electric, or remote control options for maximum convenience;
The operating mechanism is carefully sealed at the switch box's base, providing robust protection against outdoor environmental corrosion;
Showcases an innovative and simplified design featuring a restless mechanism, ensuring reliable dynamic performance, a compact structure, and an incredible service life of up to 10,000 cycles.
Main Technical Parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |