Customization: | Available |
---|---|
Breaking Capacity: | 12kv/24kv/40.5kv |
Type: | Current Fuse |
Still deciding? Get samples of US$ 30/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
(H) RW(F) series outdoor high voltage AC drop fuse, affectionately known as the "fuse," stands as a stalwart guardian for your overhead distribution systems, operating at a rated frequency of 50Hz and rated voltage of 10kV (12/15/35/40.5). This fuse is indispensable in safeguarding your circuits and electrical equipment from the perils of overloads or short circuit faults within the power system. In its vigilant state, the fuse is intricately connected in series within the power line, maintaining a tensioned posture with its movable joint securely locked. Upon detection of a line failure, the fault current swiftly prompts the fuse to blow, allowing the movable joint to release, the fuse tube drops expediently, and the circuit is effectively interrupted. This action ensures the utmost safety protection, facilitating maintenance of both line and equipment. Enhanced with elastic contact and an arc extinguishing cover, the load type fuse transcends the ordinary, adeptly handling the opening and closing of load current in power systems.
Our fuse product meets and exceeds the stringent technical standards stipulated in GB / T 15166.3 - 2008, referring to high voltage AC fuses - Part 3: injection fuses, as well as DL / T 640 - 1997 for outdoor AC high voltage drop tested fuses and fuse links, ensuring that every order aligns with precise technical conditions.
Working Environment:
Ambient temperature: A robust range from -40°C to +40°C;
Relative humidity: Daily averages capped at 95%, with monthly averages not exceeding 90%;
Proudly serving regions where the altitude remains below 3000 meters;
Designed to withstand outdoor wind speeds up to 34 meters per second;
Installation site: Optimal in areas free of fire, explosion hazards, and chemical corrosive gases, ensuring well-ventilated conditions.
Note: Should your requirements surpass these normal use conditions, a collaborative negotiation with our company will ensure tailored solutions.
Technical parameters are meticulously crafted to meet the highest standards.
Note: Customization is at the heart of our service. We fulfill product specifications according to user-defined requirements.
Model |
Voltage |
Current |
Rated maximum
breaking current |
1min power frequency dry withstand
voltage |
1min power frequency wet withstand
voltage |
Rated lightning impulse withstand
voltage |
Opening and closing
load current |
XS-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
XS-15/100(200) |
15 |
||||||
PD-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
PD-15/100(200) |
15 |
||||||
(H)RW3-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW3-12/100(200) |
12 |
||||||
(H)RW4-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW4-12/100(200) |
12 |
||||||
(H)RW7-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW7-12/100(200) |
12 |
||||||
(H)RW10-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW10-12/100(200) |
12 |
||||||
(H)RW10-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW10-12F/100(200) |
12 |
||||||
(H)RW11-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
! |
(H)RW11-12/100(200) |
12 |
||||||
(H)RW11-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW11-12F/100(200) |
12 |
||||||
(H)RW12-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
45 |
30 |
105 |
/ |
(H)RW12-12/100(200) |
12 |
||||||
(H)RW12-15/100(200) |
15 |
||||||
(H)PRWG1-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)PRWG1-12F/100(200) |
12 |
||||||
(H)RW33-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW33-15/100(200) |
15 |
||||||
(H)RW5-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)RW10-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)PRWG2-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |