Customization: | Available |
---|---|
Breaking Capacity: | 12kv/24kv/40.5kv |
Type: | Current Fuse |
Still deciding? Get samples of US$ 30/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
(H) RW(F) series outdoor high voltage AC drop fuse, affectionately known as the 'fuse,' is meticulously engineered for outdoor overhead distribution systems boasting a rated frequency of 50Hz and a rated voltage range of 10kV to 40.5kV. This cutting-edge protective element ensures safeguarding of circuits and electrical equipment against overloads or short circuit incidents within power systems. Under normal operating conditions, this state-of-the-art fuse is adeptly connected in series within the power line, maintaining tension and a securely locked movable joint. In the event of a line fault, the powerful fault current triggers the fuse to activate, releasing the movable joint while the fuse tube swiftly disengages, thereby effectively severing the circuit and offering unparalleled safety protection for line and equipment maintenance. Enhanced by an elastic contact and a sophisticated arc extinguishing cover, this load type fuse is proficient at opening and closing load currents, making it an indispensable component in power systems.
The fuse is meticulously designed to adhere to rigorous technical standards, including GB / T 15166.3 - 2008 high voltage AC fuses - Part 3: injection fuses, as well as DL / T 640 - 1997 outdoor AC high voltage drop tested fuses, and fuse links ordering technical conditions, ensuring optimal performance and reliability.
Working Environment:
Ambient temperature: Rigorously operational within a broad spectrum of -40°C to +40°C, ensuring adaptability across diverse climates;
Relative humidity: Maintains efficiency with a daily average not exceeding 95% and a monthly average not surpassing 90%, ensuring optimal functionality;
The altitude does not exceed 3000 meters, ensuring unparalleled performance even at elevated heights;
Outdoor wind speed not exceeding 34 meters/second, engineered to withstand and perform amid strong gusts;
Installation site: Ideal for locations free from fire or explosion hazards, devoid of chemically corrosive gases, and offering excellent ventilation, safeguarding longevity and safety.
Note: Should the standard usage conditions be exceeded, users are encouraged to negotiate with the company for tailored solutions.
Technical parameters
Note: Our company is committed to delivering products customized to user specifications, ensuring all needs are met with precision.
Model |
Voltage |
Current |
Rated maximum
breaking current |
1min power frequency dry withstand
voltage |
1min power frequency wet withstand
voltage |
Rated lightning impulse withstand
voltage |
Opening and closing
load current |
XS-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
XS-15/100(200) |
15 |
||||||
PD-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
PD-15/100(200) |
15 |
||||||
(H)RW3-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW3-12/100(200) |
12 |
||||||
(H)RW4-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW4-12/100(200) |
12 |
||||||
(H)RW7-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW7-12/100(200) |
12 |
||||||
(H)RW10-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW10-12/100(200) |
12 |
||||||
(H)RW10-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW10-12F/100(200) |
12 |
||||||
(H)RW11-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
! |
(H)RW11-12/100(200) |
12 |
||||||
(H)RW11-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW11-12F/100(200) |
12 |
||||||
(H)RW12-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
45 |
30 |
105 |
/ |
(H)RW12-12/100(200) |
12 |
||||||
(H)RW12-15/100(200) |
15 |
||||||
(H)PRWG1-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)PRWG1-12F/100(200) |
12 |
||||||
(H)RW33-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW33-15/100(200) |
15 |
||||||
(H)RW5-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)RW10-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)PRWG2-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |