Customization: | Available |
---|---|
Type: | High-voltage |
Structure: | Three-column Disconnector |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introducing the remarkable ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker, a paramount solution for modern outdoor distribution networks. Often referred to affectionately as the 'circuit breaker', this state-of-the-art switchgear is meticulously engineered to accommodate a 12kV rated voltage and a robust three-phase AC operating at 50Hz. This versatile circuit breaker excels in managing the interruption and reconnection of load current, overload current, and short circuit current within power grids. With its cutting-edge overload and short circuit protective features, it effortlessly caters to control and measurement needs, offering sophisticated remote control and monitoring functions. Its broad application range extends across substations, industrial sectors, and mining enterprise distribution systems, positioning it as the premier choice for environments that necessitate frequent operations, ensuring unparalleled control and efficiency.
Structural Features:
Meticulously crafted, this circuit breaker boasts a refined three-phase pillar dry design, exemplifying unparalleled precision and attention to detail.
Expertly engineered with a fully enclosed structure, it delivers outstanding sealing performance, exceptional moisture resistance, and anti-condensation properties, making it ideal for high-temperature and humid environments.
Employing state-of-the-art vacuum arc extinguishing technology, it offers exceptional insulation reliability, enhancing overall safety and performance.
Ensures impeccable opening and closing performance, guaranteeing safety with no risk of combustion or explosion, solidifying its reliability.
Designed to be compact and lightweight, this circuit breaker requires no maintenance while boasting an impressive lifespan.
Features versatile operation with options for manual, electric, or remote control, catering to diverse user requirements.
The operating mechanism is meticulously sealed at the switch box's base, effectively safeguarding against outdoor environmental corrosion.
Showcases an innovative and simplified design featuring a restless mechanism, ensuring reliable dynamic performance, a compact structure, and an astonishing service life reaching up to 10,000 cycles.
Main Technical Parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |