Introducing the ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker, a marvel in modern power management, affectionately termed the 'circuit breaker.' This outstanding piece of outdoor distribution switchgear is meticulously engineered to operate at a rated voltage of 12kV, complemented by a robust three-phase AC of 50Hz. This adaptable circuit breaker excels at managing the interruption and connection of load current, overload current, and short circuit current within the power grid with unparalleled precision. It is equipped with cutting-edge overload and short circuit protective capabilities, seamlessly integrating control and measurement specifications while providing state-of-the-art remote control and monitoring functionalities. Its extensive applications across substations, industrial sectors, and mining enterprise distribution systems make it an indispensable asset, particularly in environments demanding frequent operations, by offering unmatched control and operational excellence.
Structural Features:
Exquisitely crafted, the circuit breaker is designed with a three-phase pillar dry design, exemplifying precision engineering;
Expertly engineered with a fully enclosed structure, it provides superior sealing and exceptional moisture resistance while boasting anti-condensation properties, making it the perfect choice for challenging high-temperature and humid environments;
Utilizes state-of-the-art vacuum arc extinguishing technology, delivering outstanding insulation reliability and performance;
Ensures flawless opening and closing performance, enhancing safety by eliminating any risk of combustion or explosion;
This compact, lightweight unit demands no maintenance and offers an impressive lifespan, setting new standards in durability;
Flexible in its operation, offering manual, electric, or remote control options to suit varied operational needs;
The meticulously sealed operating mechanism at the base of the switch box provides effective protection against outdoor environmental corrosion, enhancing longevity and reliability;
Presenting a novel, simplistic design, it features a dynamic restless mechanism ensuring reliable performance, a compact form, and an astounding service life of up to 10,000 cycles.
Main Technical Parameters:
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Rated current |
A |
630 |
1250 |
||
3 |
Rated frequency |
Hz |
50 |
|||
4 |
Rated insulation level |
1min power frequency withstand voltage |
Dry test |
/ |
42/48(fracture) |
|
Wet test |
34 |
|||||
Secondary circuit to ground |
2 |
|||||
Lightning impulse withstand voltage (peak value) |
75/85(fracture) |
|||||
5 |
Rated short circuit making current (peak value) |
kA |
50 |
63 |
||
6 |
Rated short time withstand current |
kA |
20 |
25 |
||
7 |
Rated peak withstand current |
kA |
50 |
63 |
||
8 |
Breaking times of rated short circuit breaking current |
Times |
30 |
|||
9 |
Rated short circuit duration |
s |
4 |
|||
10 |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC220,AC220 ,AC/DC220 |
|||
11 |
Rated operation sequence |
/ |
Off-0.3s-on-off-180s-on-off |
|||
12 |
Rated current of over current trip |
A |
5 |
|||
13 |
Mechanical life |
second |
10000 |
|||
14 |
Allowable wear accumulative thickness of moving and static contacts |
mm |
3 |
|||
15 |
Rated current of over current release |
A |
5 |
|||
16 |
Current ratio of current transformer |
/ |
200/5 400/5 600/5 |
|||
17 |
Contact opening distance |
mm |
9±1 |
|||
18 |
Contact overtravel |
mm |
2±0.5 |
|||
19 |
Average opening speed |
m/s |
1.2±0.3 |
|||
20 |
Average closing speed |
m/s |
0.6±0.2 |
|||
21 |
Opening time |
ms |
≤40 |
|||
22 |
Closing time |
ms |
20~45 |
|||
23 |
Closing bounce time |
ms |
≤2 |
|||
24 |
Asynchrony of three phase closing and opening |
mm |
≤2 |
|||
25 |
Three phase circuit resistance |
μΩ |
≤80 Band isolation≤120 |