Customization: | Available |
---|---|
Breaking Capacity: | 12kv/24kv/40.5kv |
Type: | Current Fuse |
Still deciding? Get samples of US$ 30/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
(H) RW(F) series outdoor high voltage AC drop fuse, commonly referred to as the 'fuse,' is meticulously designed for outdoor overhead distribution systems. It operates at an optimal rated frequency of 50Hz with a rated voltage spectrum of 10kV, extending up to 12/15/35/40.5. This robust protective component is indispensable for safeguarding circuits and electrical apparatus from the detrimental impacts of overloads or short circuit mishaps within the power system. In standard operation, the fuse integrates seamlessly into the power line, maintaining a tensioned state with a securely locked movable joint. However, upon encountering a line failure, the ensuing fault current triggers the fuse to blow, leading to the release of the movable joint. This action swiftly drops the fuse tube, effectively interrupting the circuit and thereby providing essential safety protection for the maintenance of both line and equipment. Enhancing the conventional design, this load-type fuse incorporates an elastic contact alongside an arc extinguishing cover, ensuring reliable operation for opening and closing load currents within the power system.
The fuse is meticulously crafted to adhere to stringent technical standards including GB / T 15166.3 - 2008, which pertains to high voltage AC fuses - Part 3: injection fuses, as well as DL / T 640 - 1997 regarding outdoor AC high voltage drop tested fuses and fuse links ordering technical conditions.
Working Environment:
Ambient temperature: -40C to +40C;
Relative humidity: Daily average not exceeding 95%, with a monthly average not surpassing 90%;
Altitude: Must not exceed 3000m;
Outdoor wind speed should not exceed 34 meters/second;
Installation site: Must be free from fire, explosion hazards, and chemical corrosive gases, and should be well-ventilated.
Note: Should these typical usage conditions be surpassed, users are encouraged to engage in discussions with the company for tailored solutions.
Technical parameters
Note: Our company is equipped to provide products customized to meet user requirements.
Model |
Voltage |
Current |
Rated maximum
breaking current |
1min power frequency dry withstand
voltage |
1min power frequency wet withstand
voltage |
Rated lightning impulse withstand
voltage |
Opening and closing
load current |
XS-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
XS-15/100(200) |
15 |
||||||
PD-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
PD-15/100(200) |
15 |
||||||
(H)RW3-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW3-12/100(200) |
12 |
||||||
(H)RW4-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW4-12/100(200) |
12 |
||||||
(H)RW7-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW7-12/100(200) |
12 |
||||||
(H)RW10-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW10-12/100(200) |
12 |
||||||
(H)RW10-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW10-12F/100(200) |
12 |
||||||
(H)RW11-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
! |
(H)RW11-12/100(200) |
12 |
||||||
(H)RW11-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)RW11-12F/100(200) |
12 |
||||||
(H)RW12-10/100(200) |
10 |
100 (200) |
6.3 (12.5) |
45 |
30 |
105 |
/ |
(H)RW12-12/100(200) |
12 |
||||||
(H)RW12-15/100(200) |
15 |
||||||
(H)PRWG1-10F/100(200) |
10 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
10 |
(H)PRWG1-12F/100(200) |
12 |
||||||
(H)RW33-12/100(200) |
12 |
100 (200) |
6.3 (12.5) |
42 |
30 |
75 |
/ |
(H)RW33-15/100(200) |
15 |
||||||
(H)RW5-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)RW10-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |
|||||||
(H)PRWG2-35/100(200) |
35 |
100 (200) |
6.3 (12.5) |
95 |
86 |
185 |
/ |
40.5 |